Section BXM‐161‐7HE‐20A

030‐101765 Rev. B

R

7

1311IARB

Euro‐connectors, pull‐off the Euro‐connector, strip approxi­
mately 3/8” off the end of each wire, insert wire(s) into hole(s),
tighten screws, and push‐on the Euro‐connector.

1.

‐48VDC Fan Terminal Block

. The heat exchanger fans re­

quire a ‐48VDC, 1.75A power source to be wired to the
Euro‐connector located at the bottom left corner of the
Controller Card.

2.

Temperature Alarm Terminal Block

. A Normally Open Tem­

perature Alarm thermostat contact closes when the
internal cabinet temperature exceeds 60° C. For tempera­
ture alarm connections, connect alarm wiring from the
field‐provided alarm equipment to the 2‐position Euro‐
connector at the top left of the controller card.

3.

Door Alarm Terminal Block

. A Normally Open Door Alarm

contact closes when either the Network or Customer door
is opened. For door alarm connections, connect wiring
from the field‐provided alarm equipment to the 2‐position
Euro‐connector at the top left of the controller card.

Connector

Name

# of

Positions

Position

Name

Description

Left Side of Controller Card

TEMP ALARM

2

NO

Normally open

(Installer connects to field‐

provided equipment.)

COM

Common

(Installer connects to field‐

provided equipment.)

DOOR ALARM

2

NO

Normally open

(Installer connects to field‐

provided equipment.)

COM

Common

(Installer connects to field‐

provided equipment.)

FAN 

 A*

(heat exchanger fans)

2

BLK

 voltage. Factory 

connected to Heat Ex-

changer.

RED

+ voltage. Factory 

connected to Heat Ex-

changer.

ÏÏÏÏÏ

ÏÏÏÏÏ

FAN 

 B

(Not Used)

ÏÏÏÏ

ÏÏÏÏ

N/A

ÏÏÏÏ

BLK

ÏÏÏÏÏÏÏ

 voltage. Fan B.

ÏÏÏÏ

ÏÏÏÏ

RED

ÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏ

+ voltage. Fan B.

Power

Connections

2

-48V

Apply -48V

(Installer connects to field‐

provided local DC power.)

GND

System Ground

(Installer connects to field‐

provided local DC power.)

Bottom of Controller Card

DOOR INPUT

ALARM

2

BLK

Factory installed. Con-

nects to door switch.

RED

TEMP INPUT

ALARM

N/A

Factory installed. Con-

nects to temperature

sensor on controller card.

*Two fans are wired to each set of terminals.
Shaded rows indicate installer connections (TEMP ALARM, DOOR ALARM, and Power)

Table 2.    Controller Card Connectors

2.2.6

AC Duplex & GFI Outlets for Installed Equipment

In the bottom‐right rear corner of the cabinet is an AC duplex
outlet (with a 1/2” fitting below one on the cabinet exterior sur­

Figure 14.     Ground Plate & AC Duplex Outlet Locations

Ground Plate

AC duplex

outlet

GFI outlet

face) for powering any customer‐supplied AC‐powered
equipment mounted in the cabinet. When an external AC power
source is connected to this outlet, AC power also can be pro­
vided to the GFI convenience outlet in the lower‐left front
corner of the cabinet (to facilitate the installer's test equipment
powering), by installing the provided AC 3‐wire cable.

2.2.7

Grounding and Bonding Center

Boxer‐16's grounding and bonding center is located on the bot­
tom interior surface of the cabinet (Figure 14), close to the front
door. A ground plate is provided that contains eight sets of
ground posts and one copper ground lug, for cable and chassis/
earth ground. Bond equipment/cables to the ground posts per
company practice, and connect a #6 AWG chassis or earth
ground wire to the ground lug. An Electro‐Static Discharge
(ESD) wrist‐strap jack is also located on the ground plate.

3.

INSTALLATION

Use and follow local codes and company practices to install the
Westell

r

 Boxer

r

 cabinet. If none exist, use the instructions con­

tained herein. Installation consists of:

S

inspecting the unit for damages that may have incurred dur­
ing shipping,

S

following proper safety precautions,

S

reviewing pre‐mounting considerations, such as selecting
the mounting type and location, and preparing the mount­
ing site,

S

gathering all tools, materials, and equipment,

S

removing any knock‐outs where access holes are required,

S

mounting the cabinet,

S

making ground and all power connections,

S

powering up the cabinet (system power‐up),

S

mounting any customer‐supplied equipment inside the cab­
inet,

S

making communication cable connections,

S

making any desired alarm connections,

Содержание Boxer BXM1619-7HE

Страница 1: ...ocu ment adds several G models to Table 4 adds the NESC OSHA note above adds the GR 487 Issue 4 compliant bullet list feature in Paragraph 1 5 for the 7HEG model and updates Figure 4 and Figure 6 to s...

Страница 2: ...Exchanger removable and replaceable 1 5 Product Features Each Boxer 16 cabinet comes fully assembled pre wired tested and ready for field provided customer equipment installation and includes the foll...

Страница 3: ...ns and vents Security is provided via a 2 point latch a tamper proof screw lock and a padlock hasp Side wall lift ears Paragraph 2 1 2 5 are provided for temporary installation lift assistance The bot...

Страница 4: ...ed for conve nient access to the rear of equipment mounted inside Boxer 16 The purpose of the access panel is to facilitate equipment ac cess cabling and servicing The panel is secured with six tamper...

Страница 5: ...ameter knock outs in the floor of the Boxer 16 cabinet where an option al battery box attaches to the cabinet hole patterns of both units match KNOCK OUT REMOVAL NOTE Always remove knock outs where ho...

Страница 6: ...nterior of the cabinet reaches 35 C 95 F and turn off when the internal cabinet temperature cools to 25 C 77 F At the core of the heat ex change system are numerous aluminum fins visible through the c...

Страница 7: ...card Two fans are wired to each set of terminals Shaded rows indicate installer connections TEMP ALARM DOOR ALARM and Power Table 2 Controller Card Connectors 2 2 6 AC Duplex GFI Outlets for Installe...

Страница 8: ...ectrostatic discharge procedures must be followed to maintain personal and equipment safety Do not store units near magnetic electromagnetic or electrostatic fields Always store or ship units in the o...

Страница 9: ...out from either direction per hole size WEIGHT NOTE The Boxer 16 cabinet weighs 80 pounds The weight of the inter nal equipment installed in the Boxer 16 should not exceed 90 pounds The mounting surf...

Страница 10: ...mbined weight of the cabinet and the equipment mounted inside the cabinet Westell recommends a minimum cabinet installation height of 30 from the ground 1 Find best wall position Locate the best mount...

Страница 11: ...ug 11 Determine next step or close up cabinet and clean the site Repeat Steps 6 8 of Paragraph 3 6 1 to determine the next step or finish the physical cabinet installation 3 6 3 Mounting on a Pole or...

Страница 12: ...it BXA PM02 Contents Threaded rod Bracket Washers and Nuts BXA PM03 kit also includes a shelf Figure 18 Boxer Mounted on Pole with Pole Mount Kit Pole Also see the instructions in the optional BXA PM0...

Страница 13: ...and gap less suppressors The pedestal shall be capable of accepting 120 240 volts single phase and provide hardware for mounting a power meter However Boxer 16 must only be supplied with 120 volts Fo...

Страница 14: ...hole pattern accommodates a wide variety of equipment and mounting bracket hole patterns Always follow company practices and the guidelines below when mounting equipment inside the cabinet 1 Verify th...

Страница 15: ...te and verify no equipment tie downs cables or wires will interfere with the closing of the door Clean up the installation site per company practice 3 18 Closing and Locking the Cabinet Upon completio...

Страница 16: ...mpartment from the door Make a written note of the length of the old power cord RETURN UNIT NOTE Return the old defective unit to Westell and receive a replace ment new unit see Paragraph 7 2 for deta...

Страница 17: ...ensor switch into its mount ing bracket from the rear side so the door sensor button protrudes through the hole for it at the front of the mount ing bracket press or snap it into place 6 Test Verify t...

Страница 18: ...optional battery box and pole mounted with the pole mount kit see Table 4 Table 3 Boxer 16 Cabinet Physical Specifications 8 SPECIFICATIONS 8 1 Electrical and Physical Specifications The Westellr Boxe...

Страница 19: ...on 48VDC A90 BXSC1619 4H Boxer 20 20 RU 19 wide rack Main Cabinet 400W heat exchanger always on 48VDC A90 BXM2019 4HE 400W heat exchanger temp controlled 24 or 48VDC A90 BXM2019 4HE3 Same as the 4HE...

Страница 20: ...0 101765 Rev B R 20 1311IARB Appendix A Product Views Figure 24 Bottom View of Boxer 16 Cabinet Showing Dimensions and Knock outs Mounting lift brackets door and heat exchanger not shown For mounting...

Страница 21: ...Section BXM 161 7HE 20A 030 101765 Rev B R 21 1311IARB Figure 25 Front Exterior View of Boxer 16 Cabinet 24 0 33 0 24 5 41 0 39 0 Rear View Panel On...

Страница 22: ...Section BXM 161 7HE 20A 030 101765 Rev B R 22 1311IARB Figure 26 Right Side Exterior View of Boxer 16 Cabinet 33 0 18 05 20 60 28 10 41 0...

Отзывы: