 Equipment Issue A

030‐101374 Rev. A, November 2012

Section BXM‐161‐4HE‐20A

R

E

 

2012 Westell, Inc. All rights reserved.  

Westell

r

 is a registered trademark of and Boxer

t

 is a trademark of Westell, Inc.

Page 1 of 21

1211IARA

Westell

r

 Boxer

t

 BXM1619‐4HE

Outdoor Cabinet with ‐48VDC Heat Exchanger

CONTENTS

PAGE #

1. GENERAL

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2. FEATURES 3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3. INSTALLATION

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4. MAINTENANCE

15

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5. SERVICE & REPAIRS

15

. . . . . . . . . . . . . . . . . . . . . . . .

6. CUSTOMER & TECHNICAL SERVICES

17

. . . . . . . .

7. WARRANTY & RETURNS

17

. . . . . . . . . . . . . . . . . . . . .

8. SPECIFICATIONS

18

. . . . . . . . . . . . . . . . . . . . . . . . . . .

9. APPENDIX A ‐ Product Views

19

. . . . . . . . . . . . . . . . . .

1.

GENERAL

1.1

Document Purpose

This document provides general, installation, and specifica­
tion information for the Westell

r

 Boxer

t

 BXM1619‐4HE

Outdoor Cabinet with Heat Exchanger (shown in Figure 1).
This product is designed to provide Network equipment
protection in outdoor environments while providing a quick
and easy customer hand‐off. The intended audience for this
document is engineering, operations, and installation person­
nel of MSO, Telco, and utility companies. See Table 4 for
product ordering information and available options, as well as
information on the companion but optional battery box or skirt
that can be mounted under the Boxer cabinet.

‐ NOTE ‐

Hereafter, the BXM1619‐4HE 16‐RU Boxer cabinet may be re­
ferred to as the “Boxer‐16” or “cabinet.”

1.2

Document Status

Whenever this practice is updated, the reason will be stated in
this paragraph.

1.3

Product Purpose and Description

Boxer‐16 is a compact, actively‐cooled, NEMA 4 outdoor cabi­
net that can house and protect a wide range of electronic
equipment. Up to 16 vertical RUs  (28”) of 19‐inch wide inter­
nal rack space is available to house Network equipment such as
(but not limited to) multiplexers, copper bonding solutions,
Ethernet switches and media converters, xDSL boxes, and DS3
hand‐offs. Protectively mounted on the Boxer front door, sepa­
rate from the interior rack space, is a heat exchanger and fan
unit.

Boxer‐16 supports rapid equipment installation and wiring
through the use of adjustable and removable 19” rack channels.
An access panel is located at the rear of Boxer‐16 to allow easy
access to the rear of the installed equipment. To ensure easy ac­

Figure 1.

Isometric Closed View of Boxer‐16 Cabinet

cess for input and out cabling, Boxer‐16 includes ample room
below the rack space as well as various sized conduit knock‐
outs.

1.4

Product Mounting

The Boxer‐16 cabinet is typically mounted outdoors, above
ground on an H‐frame, a wall, square pedestal or post (minimum
8” wide), or a round pole (from 8” to 20” in diameter). Floor or
concrete pad mounting is supported when used with an optional
Boxer battery box or skirt. All mounting hardware must be capa­
ble of supporting the weight of the Boxer‐16 cabinet plus the
weight of any equipment mounted in it. The Boxer‐16 cabinet is
typically located at the customer premises but can be located
anywhere a compact, weather‐tight, outdoor cabinet is required.

1.5

Product Features

Each Boxer‐16 cabinet comes fully assembled, pre‐wired, tested,
and ready for field‐provided customer equipment installation,
and includes the following features and capabilities.

S

NEMA 4 compliant

S

Actively cooled with heat exchanger

S

Dissipates up to 400 watts

S

Field‐replaceable door‐mounted fans

Содержание Boxer BXM1619-4HE

Страница 1: ...onic equipment Up to 16 vertical RUs 28 of 19 inch wide inter nal rack space is available to house Network equipment such as but not limited to multiplexers copper bonding solutions Ethernet switches...

Страница 2: ...nt bracket Liquid tight fitting in access hole for heat exchanger wires Heat Exchanger Compartment unlocks with Phillips screw from inside the cabinet S 48VDC powered S Low noise level S Compact size...

Страница 3: ...commodate a variety of cable fitting or conduit sizes and types 2 1 2 1 Large Cabinet Door A full size locking door provides ample technician and equip ment access to the interior of the cabinet and a...

Страница 4: ...gure 7 Mounting Brackets for Wall H Frame Mounting Top Exterior Mounting Bracket note the keyholes Bottom Exterior Mounting Bracket note the 5 slots at the bottom The brackets are factory installed on...

Страница 5: ...nnel mounting bracket 1 of 7 position holes Loosen nuts lift and slide rack channel to desired position Rack Channel 2 2 1 Internal 19 Rack Channels Two adjustable rack channels see Figure 10 inside t...

Страница 6: ...5 External Air Fans FAN A Connector Two factory installed always on fans shown in Figure 12 to circulate cooler exterior air up through the heat exchanger are located under the cover for the heat exch...

Страница 7: ...binet Figure 14 close to the front door A ground plate is provided that contains eight sets of ground posts and one copper ground lug for cable and chassis earth ground Bond equipment cables to the gr...

Страница 8: ...lies not provided are required to mount the Boxer 16 cabinet Door Opening Locking Tools V 7 16 can wrench or 216 tool V Padlock optional Knock Out Removal Tools V Hammer V Punch V Pliers Cabinet Mount...

Страница 9: ...he mounting steps All knock outs should be knocked out from the inside of the cabinet except for the small 0 575 knock outs which are to be knocked out from the outside of the cabinet and except for t...

Страница 10: ...inet and clean the site Close the Boxer 16 door and lock it using a can wrench or 216 tool and an op tional padlock Pick up any tools and materials at the installation site and clean the site of any t...

Страница 11: ...und rod or wire 6 AWG must enter the cabinet and be connected to the ground lug located on the interi or ground plate Make all ground connections prior to any telecommunications cable connections Grou...

Страница 12: ...nnecting 48VDC Fan Power Follow the steps below to connect 48VDC fan power from a 48VDC power source to the Euro connector in the Controller Figure 20 Euro Connectors for Field Connections Pull off co...

Страница 13: ...agraph 3 10 if it is also desired to wire Boxer 16 s GFI convenience outlet 6 Fish or route wires Fish or route the AC wires from the power source through the conduit to the Boxer 16 cabinet routing t...

Страница 14: ...le connections at the inside rear of the cabinet The panel is secured with hex nut in cup screws 3 14 Connecting Communication Cables The types of communication cables used and their connector types i...

Страница 15: ...mbly CAUTION To avoid electrical shock turn off any DC or AC power feeds to the panel before removing or replacing the controller card 5 1 Replacing the Controller Card The Controller Card cannot be f...

Страница 16: ...tor 14 Apply power and test If not already installed re install the fuse in the controller card and apply power to the cabinet Verify the fans are working properly 5 3 Replacing the Inside Air Fans Fa...

Страница 17: ...he mounting bracket Connect the wires into their proper positions in the new switch Insert the new door sensor assembly into its mount ing bracket from the rear side so the door sensor button protrude...

Страница 18: ...g 16RU 19 rack AC GFI out lets screw down rear access panel Other Boxer Cabinets A90 BXM3019 NAF Boxer 800W 48VDC fan cooled 30 RU 19 rack AC GFI outlets screw down rear access panel A90 BXM2019 4HE B...

Страница 19: ...101374 Rev A R 19 1211IARA Appendix A Product Views Figure 24 Bottom View of Boxer 16 Cabinet Showing Dimensions and Knock outs Mounting lift brackets fan cooling and door handle not shown For mountin...

Страница 20: ...Section BXM 161 4HE 20A 030 101374 Rev A R 20 1211IARA Figure 25 Front Exterior View of Boxer 16 Cabinet 24 0 33 0 24 5 41 0 39 0 Rear View Panel On...

Страница 21: ...Section BXM 161 4HE 20A 030 101374 Rev A R 21 1211IARA Figure 26 Right Side Exterior View of Boxer 16 Cabinet 33 0 18 05 20 60 28 10 41 0...

Отзывы: