11.2 Smart-Grid
With the Smart-Grid function (SG Ready), the heat pump can be operated with
electricity supplied by a photovoltaic system.
Switching conditions
Observe wiring diagram [ch. 5.5].
The Smart-Grid function offers the following possibilities:
Operating mode
Function
Input H1
Input H2
1: Block (EVU block)
Heating operation and DHW loading
blocked, frost protection is provided.
closed
open
2: Normal operation
DHW loading and heating operation are
controlled to setpoint temperature.
open
open
3: Increased operation
(over-supply of electricity)
The
SG Ready increase
is added
to the flow setpoint temperature in the
heating circuit and the DHW setpoint
temperature.
The increase for:
heating operation
DHW loading [ch. 6.7.4.5]
open
closed
4: Forced operation
(over-supply of electricity)
Heat pump and electric heating are in
operation in heating mode until the re-
spective maximum temperature has been
reached.
closed
closed