Installation and operating instruction
Hydraulic unit WWP LS 8 ... 16-B
6 Operation
83306902 2/2017-05 La
53-88
6.7.4.4 Legionella protection
Domestic hot
water
Legionella
protection
The menu is only displayed in the Expert level.
Parameters
Setting
Day
Off:
Legionella protection deactivated.
Mon-Sun, all
:
Weekday on which Legionella protection is carried out.
Time
Time for the start of Legionella protection.
Temperature
DHW setpoint temperature for Legionella protection.
Loading time
Maximum duration for Legionella protection.
Off:
Legionella protection is not cancelled.
5 … 240min
:
If the DHW setpoint temperature for Legionella protection is not reached in the
time set, Legionella protection is cancelled.
6.7.4.5 Settings
Domestic hot
water
Settings
Parameters
Setting
SG Ready increase
Increase of the DHW setpoint temperature with Smart-Grid function in operating
mode 3 [ch. 11.2].
Maximum temperature
Upper limit value of DHW setpoint temperature with Smart-Grid function in operat-
ing mode 4 [ch. 11.2].
Flow increase
Temperature increase of DHW setpoint for DHW loading.
Flow setpoint temperature = DHW setpoint tempe
flow increase