Installation and operating instruction
Oil burner WL40Z-A 1LN
6 Operation
83298902 2/2019-05 La
28-112
6 Operation
6.1 Operating panel
1
2
3
4
1
[–]
Change values
2
[+]
3
[L/A] Air
Select air damper actuator
4
[Enter]
Reset burner:
call up information
press for approx. 0.5 seconds: Info level
press for approx. 2 seconds: Service level
2
and
4
[+] and [ENTER]
press simultaneously for approx. 2 seconds:
Parameter level (only possible with display
OFF
)
3
and
4
[L/A] and [Enter]
press simultaneously: select fan speed (only in
conjunction with variable speed drive)
Various actions are only triggered when the key is released, for example changing
the display, reset.
OFF function
Press [ENTER], [L/A] and [G] keys simultaneously.
Immediate lockout with error
18h
.
Operating level
The current air damper setting and/or the fan speed can be displayed in the operat-
ing level (
10
).
Displaying air damper setting:
Press key [L/A].
Displaying fan speed:
(only in conjunction with variable speed drive)
Press [Enter] and [L/A] simultaneously.
Flame signal
The flame signal can be displayed during commissioning (setting level) by using a
combination of keys.
Press [Enter], [L/A] and [G] keys simultaneously.
The flame signal is displayed.
Recommended flame signal, see Service level information
19
Содержание WL40Z-A 1LN
Страница 1: ...Installation and operating instruction Oil burner WL40Z A 1LN 83298902 2 2019 05 ...
Страница 91: ...Installation and operating instruction Oil burner WL40Z A 1LN 12 Project planning 83298902 2 2019 05 La 91 112 ...
Страница 106: ...Installation and operating instruction Oil burner WL40Z A 1LN 14 Notes 83298902 2 2019 05 La 106 112 14 Notes ...
Страница 107: ...Installation and operating instruction Oil burner WL40Z A 1LN 14 Notes 83298902 2 2019 05 La 107 112 ...
Страница 111: ...83298902 2 2019 05 La ...