Installation and operating instruction
Oil burner WL40/1-A Z-1LN-A
7 Commissioning
83319702 1/2020-10 La
42-116
7.1.3 Setting values
Set mixing head relative to the combustion heat rating required. For this, the dif-
fuser setting and the air damper setting should be matched.
Determine diffuser setting and air damper setting
Do not operate the burner outside of the capacity graph [ch. 3.4.6].
Determine the diffuser setting (dimension X) and air damper setting required
from the diagram and note down.
Example
Burner capacity stage 2 / stage 1 required
415 kW / 270 kW
Diffuser setting (dimension X)
26.0 mm
Air damper setting stage 2 / stage 1
65° / 38°
Diffuser default settings
100
425 450 475 500 525
400
375
350
325
300
275
250
225
200
175
150
125
4
6
8
10
12
14
16
18
20
22
24
26
28
2
1
1
Combustion heat rating [kW]
2
Diffuser settings (dimension X) [mm]