Installation and operating instruction
Gas burner WG30…/1-C ZM-LN
7 Commissioning
83299902 1/2019-02 La
54-124
7. Adjust ignition load
Press [-] key.
Burner drives to operating point P
0
(ignition position).
Check combustion values in operating point P
0
(ignition position).
Set O
2
content of 4 … 5 % above gas butterfly valve setting [G].
Check mixing pressure
The mixing pressure in ignition position must be between 0.5 2.0 mbar.
If necessary, adjust mixing pressure via air damper setting [L/A].
Press [+] key.
Burner drives to operating point P
1
.
Press [ENTER].
Combustion manager changes to linearisation mode.
Confirm with [+] key.
Linearisation is initiated.
The display then shows operating point P
1
.
Calculation from P
1
to P
9
was carried out.