6 Operation
83054802 1/2018-07 La
128-228
6.12.8 Control parameters of internal load controller
Param & Display
LoadController
ControlParam
ContrlParamList
StandardParam
P-Part (Xp)
I-Part (Tn)
D-Part (Tv)
To be able to use the internal load controller, it must be activated in parameter
LC_OptgMode
The control behaviour of the load controller is set in menu
ControlParamList
.
Under
StandardParam
one of five standard parameter sets or the PID para-
meter set from the adaption can be selected.
Parameter set
StandardParam
P-Part Xp [%]
I-Part Tn[s]
D-Part Tv [s]
Adaption
Values determined during adaption [ch. 6.12.15].
very fast
42.5
68
12
fast
14.5
77
14
normal
6.4
136
24
slow
4.7
250
44
very slow
3.4
273
48
Adapting control parameters
The PID parameter can be altered manually.
Parameters
Function
P-Part (Xp)
Proportional part
I-Part (Tn)
Integral part (integral action time)
D-Part (Tv)
Differential part (derivative action time)
Xp too small
Xp too large
Tn, Tv too small
Tn, Tv too large