Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
120-228
6.12.2 Load controller operating mode
Param & Display
LoadController
Configuration
LC_OptgMode
or
Param & Display
SystemConfig
LC_OptgMode
The parameters in menu
LC_OptgMode
stipulates, wether the internal or an ex-
ternal load controller is used and which source specifies the setpoint.
External load controller
Setting
Function
ExtLC X5-03
External load controller at input X5-03 [ch. 3.3.16].
ExtLC X62
External load controller with analogue load signal at input X62 [ch. 3.3.17]. In-
put X62 must be matched to the analogue signal in parameter
Ext Inp X62
U/I
The internal load controller converts the analogue signal into a digital load signal.
This operating mode is not possible without the internal load controller.
ExtLC Bus
External load controller via Bus connection [ch. 3.3.18].