background image

KNX IP LineMaster 760 

WEINZIERL ENGINEERING GmbH 

EN 

2014-07-01 

 

Page 4/6 

Filter: 

The  physical  address  is  used  to  check 
whether  the  received  physically  ad-
dressed  telegram  should  be  routed  to 
KNX. 

 
Broadcast telegrams: 
Block: 

No  received  broadcast  telegrams  are 
routed to KNX. 

Route: 

All  received  broadcast  telegrams  are 
routed to KNX. 

 
Resending of group telegrams: 
Disable

Group telegrams are not resent to KNX in 
case of a fault. 

Enable: 

Group  telegrams  are  resent  up  to  three 
times in case of a fault. 

 
Resending of physically addressed telegrams: 
Disable: 

Physically  addressed  telegrams  are  not 
resent to KNX in case of a fault. 

Enable: 

Physically  addressed  telegrams  are  re-
sent up to three times in case of a fault. 

 
Resending of broadcast telegrams: 
Disable: 

Broadcast  telegrams  are  not  resent  to 
KNX in case of a fault. 

Enable: 

Broadcast  telegrams  are  resent  up  to 
three times in case of a fault. 

 
ETS Connection Manager 

 
The KNX IP LineMaster 760 can only act as an interface 
to KNX when the IP-configuration is valid. 
 
The following configuration steps are required: 
 
Select the button ‘Settings’ on the tab ‘Communication’ in 
the  main  window  of  ETS4.  All  available  connections  are 
listed under ‘Discovered connections’. Select the desired 
connection. 
 
The KNX IP LineMaster 760 supports up to 5 simultane-
ous tunneling connections. Each connection uses its own 
physical  address.  The  address  of  the  first  tunneling  con-
nection  can  be  changed  within  the  ‘Local  Interface  Set-
tings’. 
 

 

 
Physical  addresses  of  the  additional  tunneling  connec-
tions  can  be  assigned  directly  on  the  device. 
This  is  done  by  pressing  the  programming  key  on  the 
device (2) longer than one second. After that, the Learn-
LED  will  start  blinking,  which  indicates  that  the  assign-
ment of the additional addresses was successful. 
 
The additional addresses are assigned as follows: 
 
Tunneling connection 2 receives the next higher address 
than  tunneling  connection  1,  tunneling  connection  3  the 
next higher address than tunneling connection 2 etc.. 
 
 

For example: 
Device address:  1.1.0     (address within ETS topology) 
Connection 1: 

1.1.250 (address within local settings) 

Connection 2: 

1.1.251 (assigned by programming key) 

Connection 3: 

1.1.252 (assigned by programming key) 

Connection 4: 

1.1.253 (assigned by programming key) 

Connection 5: 

1.1.254 (assigned by programming key) 

 
All  addresses  have  to  be  unique  and  valid  within  the 
LineMaster’s  sub  line.  Note:  be  careful  not  to  assign  the 
same  address  as  the  device  address  for  a  connection. 
The  device  address  can  be  changed  within  the  topology 
view of the ETS software. 
 
For  new  devices  (i.e.  in  the  factory  settings  state),  only 
the additional individual address of the first connection is 
active  with  the  address  15.15.250.  To  support  multiple 
concurrent  connections  additional address  assignment is 
required. 
 
Installation and connection 

 
The KNX IP LineMaster 760 is designed for installation in 
a  rack  with  a  depth  of  7  units  (126  mm).  It  contains  the 
following display and control elements: 
 

KNX LineMaster

760

1

2

3

4

5

 

 
1: 

LAN socket (RJ45, for Ethernet patch cable) 

2: 

Programming key and programming – LED 

3: 

Bus connection (KNX clamp) 

4: 

Input for mains voltage, 230V AC / 50 Hz, L / N / PE 

5: 

Output auxiliary voltage, 24V DC 

Содержание KNX IP LineMaster 760

Страница 1: ...ster as a line coupler Switch LAN EIB KNX 1 1 0 1 2 0 1 2 1 1 2 6 1 2 5 1 2 4 1 2 3 1 2 2 1 1 1 1 1 6 1 1 5 1 1 4 1 1 3 1 1 2 KNX IP LineMaster KNX LineMaster 760 KNX LineMaster 760 1 0 0 2 0 0 EIB KNX 2 1 0 2 2 0 2 2 1 2 2 6 2 2 5 2 2 4 2 2 3 2 2 2 2 1 1 2 1 6 2 1 5 2 1 4 2 1 3 2 1 2 Fig 2 KNX IP LineMaster as a backbone coupler Switch LAN EIB KNX 1 1 0 1 2 0 1 2 1 1 2 6 1 2 5 1 2 4 1 2 3 1 2 2 1...

Страница 2: ...on there must be a DHCP server in the LAN many DSL routers have an inte grated DHCP server Manual In this case the IP address the subnet and the gateway IP address must be en tered manually IP configuration IP Routing Multicast Address This address is used for routing telegrams on IP The multicast IP address 224 0 23 12 was reserved KNXnet IP at the IANA Internet Assigned Numbers Authority for thi...

Страница 3: ...eceived group telegrams from KNX if they are routed to IP Acknowledge ACK of physically addressed telegrams Always An acknowledge is generated for every received physically addressed telegram from KNX Only if routed An acknowledge is only generated for received physically addressed group tel egrams from KNX if they are routed to IP Answer with NACK Every received physically addressed telegram from...

Страница 4: ...additional tunneling connec tions can be assigned directly on the device This is done by pressing the programming key on the device 2 longer than one second After that the Learn LED will start blinking which indicates that the assign ment of the additional addresses was successful The additional addresses are assigned as follows Tunneling connection 2 receives the next higher address than tunnelin...

Страница 5: ...set is active No Reset not activated The pow er supply system works in normal operation 30 seconds A reset of 30 seconds is start ed Afterwards the line is sup plied with voltage as usual During the reset state which lasts 30 seconds the basic setting displays Reset active XX sec countdown The button returns to the previous menu level Data memory Basic setting KNX LineMaster IP Router Power S Norm...

Страница 6: ...displayed The button returns to the previous menu level Language Basic setting KNX LineMaster IP Router Power S Normal Operation Diagnostics The main section will be shown when the button is pressed once Line Reset Data Memory Operating Data Language Move the cursor flashing rectangle at right edge to the Language menu with the and buttons and and confirm with the button Sprache Deutsch Language E...

Отзывы: