background image

©

2019 WEINZIERL ENGINEERING GmbH 

Page 3/8

 

The KNX IP Router has a filter table and thus contributes to 
reducing the bus load. The filter table (8kB) supports the extend-
ed group address range (main groups 0..31) and is automatically 
generated by the ETS. 

Because of the speed difference between the Ethernet (10/100 
MBit/s) and KNX TP (9.6 kBit/s), a far greater number of tele-
grams can be transmitted on IP. If several consecutive telegrams 
are transmitted for the same line, they must be buffered in the 
router to avoid telegram loss. The KNX IP Router 752 

secure

 

has a memory for 150 telegrams (from IP to KNX). 

 

Bus access function (KNXnet/IP Tunneling) 

The KNX IP Router 752 

secure

 can be used as an interface to 

KNX. The KNX bus can be accessed from any point in the LAN. 
For this purpose, an additional individual address must be as-
signed. This is described in the following sections. 

 

Installation and Connection 

The KNX IP Router 752 

secure

 is designed for installation on a 

DIN rail with a width of 1 unit (18mm). It features the following 
controls and displays: 

 

 
 
 
 
 
 
 
 
 
 

 

 

The KNX IP Router 752 

secure

 is powered by the KNX bus. An 

external power supply is not necessary. 

 
The device is not working without bus power.

 

 

KNX Programming mode  

The KNX programming mode is activated/deactivated either by 
pressing the flushed KNX programming button 

❸ 

or by simulta-

neously pressing the buttons 

❼ 

and 

 

Status display 

The KNX LED 

❹ 

lights up green if the device is successfully 

powered by the KNX bus. This LED indicates telegram traffic on 
the KNX bus by flickering.  

Communication failures (e.g. repetitions of telegrams or telegram 
fragments) are indicated by a short change of the LED color to 
red. 

Overview of the different indications of the KNX LED 

 

The IP LED 

 lights up when an Ethernet link is active. This 

LED is green if the device has valid IP settings (IP address, Sub 
net and Gateway). With invalid or nonexistent IP settings the 
LED is red. This is also the case if e.g. the device has not yet 
received the IP settings by a DHCP server. 

This LED indicates IP telegram traffic by flickering. 

Overview of the different indications of the IP LED 

 

For testing purposes (for example, during commissioning) the 
configured routing settings (filter or block) can be bypassed via 
manual operation. 

With the button Pass GAs 

 

the forwarding of group addressed 

telegrams can be activated. 

With the button Pass IAs

    

 the forwarding of individually ad-

dressed telegrams can be activated. 

This is visualized with a single flash of the Mode LED 

❺ 

(or-

ange). If both modes are activated the Mode LED 

❺ 

flashes two 

times. 

Pressing button Pass GAs 

 

or button Pass IAs

    

❽ 

again these 

settings can be selected and deselected on demand. Via the 
Escape function (Esc) the manual operation can be stopped by 
simultaneously pressing the buttons Pass GAs 

 and Pass IAs 

If neither programming mode nor manual mode are active the 
LED 

❺ 

can visualize configuration errors. 

Overview of the different indications of the Mode LED 

 
Factory default settings 

 
The following configuration is set by factory default: 

Individual device address:  

 

 

15.15.0

 

Number of configured KNXnet/IP tunneling con.: 

Individual address of tunneling con.: 

  

15.15.240

 

IP address assignment:  

 

 

DHCP 

Initial Key (FDSK)   

 

 

active 

Security Modus 

 

 

 

not active 

 

LED Status 

Meaning 

LED lights green 

Device is working in standard operation mode. 

LED light red 

Programming mode is active 

LED flashes 1x orange 

Programming mode is not active. 
Manual operation is active. 
Forwarding IA 

or

 GA 

LED flashes 2x orange 

Programming mode is not active. 
Manual operation is active. 
Forwarding IA 

and

 GA 

LED flashes red 

Programming mode is not active. 
Manual operation is not active. 
The device is not properly loaded e.g.  
after an interrupted download. 

LED Status 

Meaning 

LED lights green 

KNX bus voltage available. 

LED flickers green 

Telegram traffic on the KNX bus 

LED shortly red 

Communication failures on the KNX bus 

LED Status 

Meaning 

LED lights green 

The device has an active Ethernet link and valid IP 
settings. 

LED lights red 

The device has an active Ethernet link and invalid IP 
settings or not yet received the IP settings by a DHCP 
server. 

LED flickers green 

IP telegram traffic 

 

 KNX bus connector 

 

Programming LED 

 

Button f. programming mode 

 KNX LED (multicolor) 

 Mode LED (multicolor) 

 IP LED (multicolor) 

 Button Pass GAs 

❽ 

Button Pass IAs 

 LAN Connector 

 
 

❻ 

752

K

N

X

IP

 R

o

u

te

s

e

c

u

re

WEINZIERL

KNX

Mode

IP

Pass
G As

Pass
I As

P/Esc

 

Содержание 5249

Страница 1: ... and send valid telegrams A time stamp in the routing telegram ensures that no previously recorded telegrams can be replayed This prevents the so called replay attack The key for the routing communication is reassigned by ETS for each installation If KNX IP Security is used for routing all con nected KNX IP devices must support security and be configured accordingly KNX IP Security for the interfa...

Страница 2: ...upler If the individual address is in the form of x y 0 x y 1 15 the router operates as a line coupler If it is in the form of x 0 0 x 1 15 the router acts as a backbone coupler Switch LAN KNX IP Router 752 secure 1 0 0 KNX IP Router 752 secure 2 0 0 KNX TP 1 1 0 1 2 0 1 2 1 1 2 6 1 2 5 1 2 4 1 2 3 1 2 2 1 1 1 1 1 6 1 1 5 1 1 4 1 1 3 1 1 2 KNX TP 2 1 0 2 2 0 2 2 1 2 2 6 2 2 5 2 2 4 2 2 3 2 2 2 2 1...

Страница 3: ...indications of the IP LED For testing purposes for example during commissioning the configured routing settings filter or block can be bypassed via manual operation With the button Pass GAs the forwarding of group addressed telegrams can be activated With the button Pass IAs the forwarding of individually ad dressed telegrams can be activated This is visualized with a single flash of the Mode LED ...

Страница 4: ...ace function the device contains additional individu al addresses that can be set in the ETS When a client e g ETS sends via the KNX IP Router telegrams to the bus they contain a sender address as one from the additional addresses Each address is associated with a connection Thus response telegrams can be clearly transmitted to the respective client The additional individual addresses must be sele...

Страница 5: ...dresses for the interface connections are displayed in the topol ogy view Each individual KNX address can be changed by clicking on the list entry and typing in the desired address into the Individual Address text field If the text field frame switches to color red after entering the address the address is already taken within your ETS project Make sure that none of the addresses above are already...

Страница 6: ...nzierl de ETS parameter dialogue The following parameters can be set using the ETS General settings Prog mode on device front In addition to the normal programming button the device allows activating the programming mode on the device front without opening the switchboard cover The programming mode can be activated and deactivated via pressing simultaneously both buttons and This feature can be en...

Страница 7: ...whether the received group telegram should be routed to KNX Group telegrams main group 14 to 31 Block No group telegrams of main groups 14 to 31 are routed to KNX Route All group telegrams of the main groups 14 to 31 are routed to KNX Filter The filter table is used to check whether the received group telegram should be routed to KNX Individually addressed telegrams Block No individually addressed...

Страница 8: ...rm downloads via IP Open Source Licenses This product contains open source software license curve25519 donna Curve25519 elliptic curve public key func tion Source http code google com p curve25519 donna Copyright 2008 Google Inc All rights reserved Redistribution and use in source and binary forms with or with out modification are permitted provided that the following condi tions are met Redistrib...

Отзывы: