If wiring is to be exposed to lightning or surges, use appropriate surge 
suppression devices. 
Keep AC, high energy, and rapidly switching DC wiring separate from 
signal wires. 
Equip ungrounded DC supplies with a resistor and capacitor in parallel to 
earth ground. This provides a path for static and high frequency 
dissipation. Typical values to use are 1MOhm and 4700pF. 

 

Caution ! 
 

To prevent the HMI from becoming damaged or having sound output 
issues, after turning the device off, please wait 10 seconds before turning 
the device on again. 

 

55

Connection 

 

Connect pos

To make a connection, strip about 3/8” of insulation off the end of the 
wire, turn the connector screw counterclockwise until the gap is wide 
open, insert the wire all the way in, and turn the screw clockwise until it’s 
tight. 

itive DC line to the ‘+24V’ terminal and the DC ground to the 

‘0V‘ terminal. 

12

2.2.2 Grounding Requirements 

 

 

Chassis ground must be used.    DC ground is not directly coupled to Earth 
ground internally. It is preferable not to ground DC negative return to chassis 
ground as poor site earths can introduce noise into a system, but if necessary 
an earth connection should be made, from the power supply return point to 
the central star earth point. Ground conductors should be as short and as large 
in size as possible. The conductors must always be large enough to carry the 
maximum short circuit current of the path being considered. Ground 
conductors should be connected to a tree from a central star earth ground 
point. This ensures that no ground conductor carries current from any other 
branch. 

13

2.2.3 CE Requirements 

To make an MT-600/8000 comply with EMC directives, and to reduce susceptibility to electrical 

interference, a separate #14 AWG ground wire should be taken to the chassis ground terminal of the 
power connector. This ground connection should be run directly to the central star earth connection 
point (as recommended in most Installation Instructions). 

14

2.2.4 Safety Guidelines 

This section presents recommended installation practices, and procedures. Since no two 

applications are identical, these recommendations should be considered as guidelines. 

Hardware 

58

Considerations 

WARNING! 
The system designer should be aware that devices in Controller systems 
could fail and thereby create an unsafe condition. Furthermore, electrical 
interference in an operator interface, such as an MT-600/8000, can lead to 
equipment start-up, which could result in property damage and/or physical 
injury to the equipment operator. 
If you, or your company, use any programmable control systems that require 
an operator or attendant, you should be aware that this potential safety hazard 
exists and take appropriate precautions. Although the specific design steps 
depend on your particular application, the following precautions generally 
apply to installation of solid-state programmable control devices. In addition, 
these precautions conform to the guidelines for installation of Controllers as 
recommended in the NEMA ICS 3-304 Control Standards. 

Programming 
Considerations 
 

To conform with ICS Safety Recommendations, checks should be placed 
in the controller to ensure that all writable registers that control critical 
parts of plant or machinery have limit checks built into the program, with 
an out-of-limit safe shut down procedure to ensure safety of personnel. 

ICS 3-304.81 Safety Recommendations: 

Consideration should be given to the use of an emergency stop function, which is independent of the programmable controller. 
      Where the operator is exposed to the machinery, such as in loading or unloading a machine tool, or where the machine 
cycles automatically, consideration should be given to the use of an electromechanical override or other redundant means, 

3

 

Содержание MT-8104iH

Страница 1: ...has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper...

Страница 2: ...or high humidity are present This will cause condensation of water in the device z Do not install these terminals in environments where have inflammable gases 5 2 2 Power Connections Make sure that al...

Страница 3: ...round terminal of the power connector This ground connection should be run directly to the central star earth connection point as recommended in most Installation Instructions 1 4 2 2 4 Safety Guideli...

Страница 4: ...s The COM light on the front of the MT 600 8000 will turn on with each Ethernet communication Shielded cable must be used for long lengths or cables run in an electrically noisy environment Do not run...

Страница 5: ...MT8070iH MT8100i and MT8104iH 1 Using USB cable mini side plug to HMI and another side plug into PC The PC will display Found New Hardware Wizard dialog Select Install from a list or specific location...

Страница 6: ...ries will jump to Touch Adjust Touch screen calibration mode After calibration the pop up window appears as the illustration below Users will be inquired restoring the system password to the default v...

Страница 7: ...000 hr min Touch panel 4 wires resistive type Touch Accuracy Active Area Length X 2 Width Y 2 Surface Hardness 4H I O port COM1 RS 232 RS 485 2W 4W COM2 RS232 COM3 RS 232 RS 485 2W Ethernet port 10 1...

Страница 8: ...f f COM1 RS232 COM2 RS232 COM3 RS485 COM3 RS232 COM1 RS485 2 4W RESET FUSE GND 24V DIP SW FUSE5X20 g h k i j b 257mm 10 12 199mm 7 83 a Com1 RS485 Com3 RS485 Com3 RS232 g USB Client port b USB Host po...

Отзывы: