Caution 
Supply Voltage 
Condition 

Do not power the MT-600/8000 and inductive DC loads

, or input 

circuitry to the controller, with the same power supply. Note: The 24 VDC 
output from some controllers may not have enough current to power the 
MT-600/8000. 

 

Caution  
Wire Routing 

Wire lengths should be minimized (Maximum 1600’ (500 m) shielded, 
1000’ (300 m) unshielded). 
Wires should be run in pairs with a neutral or common paired with a hot or 
signal line. 
If wiring is to be exposed to lightning or surges, use appropriate surge 
suppression devices. 
Keep AC, high energy, and rapidly switching DC wiring separate from 
signal wires. 
Equip ungrounded DC supplies with a resistor and capacitor in parallel to 
earth ground. This provides a path for static and high frequency 
dissipation. Typical values to use are 1MOhm and 4700pF. 

 

Caution  
 

To prevent the HMI from becoming damaged or having sound output 
issues, after turning the device off, please wait 10 seconds before turning 
the device on again. 

 

Connection 

 

To make a connection, strip about 3/8” of insulation off the end of the 
wire, turn the connector screw counterclockwise until the gap is wide 
open, insert the wire all the way in, and turn the screw clockwise until it’s 
tight. 
Connect positive DC line to the ‘+24V’ terminal and the DC ground to the 
‘0V‘ terminal. 

2.2.2 Grounding Requirements 

 

 

Chassis ground must be used.    DC ground is not directly coupled to Earth 
ground internally. It is preferable not to ground DC negative return to chassis 
ground as poor site earths can introduce noise into a system, but if necessary 
an earth connection should be made, from the power supply return point to 
the central star earth point. Ground conductors should be as short and as large 
in size as possible. The conductors must always be large enough to carry the 
maximum short circuit current of the path being considered. Ground 
conductors should be connected to a tree from a central star earth ground 
point. This ensures that no ground conductor carries current from any other 
branch. 

2.2.3 CE Requirements 

 
To make an MT-600/8000 comply with EMC directives, and to reduce susceptibility to electrical 

interference, a separate #14 AWG ground wire should be taken to the chassis ground terminal of the 
power connector. This ground connection should be run directly to the central star earth connection 
point (as recommended in most Installation Instructions). 

 

2.2.4 Safety Guidelines 

This section presents recommended installation practices, and procedures. Since no two 

applications are identical, these recommendations should be considered as guidelines. 

 

Hardware 
Considerations 

WARNING! 

The system designer should be aware that devices in Controller systems could 
fail and thereby create an unsafe condition. Furthermore, electrical 
interference in an operator interface, such as an MT-600/8000, can lead to 
equipment start-up, which could result in property damage and/or physical 
injury to the equipment operator. 

If you, or your company, use any programmable control systems that require 
an operator or attendant, you should be aware that this potential safety hazard 
exists and take appropriate precautions. Although the specific design steps 
depend on your particular application, the following precautions generally

Содержание MT-8070iH

Страница 1: ...00 8000 Series has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper wire routing and grounding will insure proper operation Mechanical Environment Avoid installing units in environments where severe mechanical vibration or shocks are present 2 0 Instal...

Страница 2: ...le gases vapors or dusts z The unit should not be installed where fast temperature variations and or high humidity are present This will cause condensation of water in the device z Do not install these terminals in environments where have inflammable gases 2 2 Power Connections Make sure that all local and national electrical standards are met when the installing the unit Contact your local author...

Страница 3: ...e noise into a system but if necessary an earth connection should be made from the power supply return point to the central star earth point Ground conductors should be as short and as large in size as possible The conductors must always be large enough to carry the maximum short circuit current of the path being considered Ground conductors should be connected to a tree from a central star earth ...

Страница 4: ...tended as safeguards against the failure of critical components and the effects of such failures or the inadvertent errors that might be introduced if programs are changed while the equipment is in operation z The ICS 3 304 81 Safety Recommendations are reproduced by permission of the National Electrical Manufacturers Association from NEMA ICS 3 304 2 3 Communications Connections The ports as you ...

Страница 5: ... by the USB 2 0 client port Support USB 2 0 client interface The cable regulation must accord with HI SPEED USB Revision 2 0 SHIELDED How to install USB driver of HMI i series i Series HMI support the function of using Mini USB cable to download projects from PC It is necessary to install USB driver of HMI on PC before at the first time enjoying this function The HMI models MT6050i MT6056i MT6070i...

Страница 6: ...n parameter will store at Flash Rom z If losing or forgetting system passwords users can set Dip Switch 1 to ON position the rest of Dips remain on OFF position and then reboot MT8000 series Under this situation MT8000 series will jump to Touch Adjust Touch screen calibration mode After calibration the pop up window appears as the illustration below Users will be inquired if restoring the system p...

Страница 7: ...2 2005 z EN 55024 1998 A1 2001 A2 2003 3 0 Specifications MT6070iH MT8070iH MT607i Hardware Specification Display 7 TFT LCD Brightness 300 cd m2 Color 65 536 colors Contrast Ratio 500 1 Resolution WxH dots 800 x 480 Back light LED Backlight life time avg 30 000 hr min Touch panel 4 wires resistive type Touch Accuracy Active Area Length X 2 Width Y 2 I O port COM1 RS 232 RS 485 2W 4W COM2 RS232 COM...

Страница 8: ...g current leakage from machine platform and incorrect input power c If the product has been maintained in a manner not conforming to product s instructions or has been modified in any way d If the serial number has been defaced or removed 4 0 Dimensions of MT 607i MT 6070iH MT 8070iH Cutout dimensions 192mm 7 559 W x 138mm 5 433 H Front View Rear View Bottom View a DIP SW Reset button g Com1 RS485...

Отзывы: