Caution  
Wire Routing 

Wire lengths should be minimized (Maximum 1600’ (500 m) shielded, 
1000’ (300 m) unshielded). 
Wires should be run in pairs with a neutral or common paired with a hot or 
signal line. 
If wiring is to be exposed to lightning or surges, use appropriate surge 
suppression devices. 
Keep AC, high energy, and rapidly switching DC wiring separate from 
signal wires. 
Equip ungrounded DC supplies with a resistor and capacitor in parallel to 
earth ground. This provides a path for static and high frequency dissipation. 
Typical values to use are 1MOhm and 4700pF. 

 

Connection 

To make a connection, strip about 3/8” of insulation off the end of the wire, 
turn the connector screw counterclockwise until the gap is wide open, insert 
the wire all the way in, and turn the screw clockwise until it’s tight. 

Connect positive DC line to the ‘+24V’ terminal and the DC ground to the 
‘0V‘ terminal. 

 

2.2.2 Grounding Requirements 

 

 

Chassis ground must be used.    DC ground is not directly coupled to Earth 
ground internally. It is preferable not to ground DC negative return to chassis 
ground as poor site earths can introduce noise into a system, but if necessary 
an earth connection should be made, from the power supply return point to 
the central star earth point. Ground conductors should be as short and as large 
in size as possible. The conductors must always be large enough to carry the 
maximum short circuit current of the path being considered. Ground 
conductors should be connected to a tree from a central star earth ground 
point. This ensures that no ground conductor carries current from any other 
branch. 

 

2.2.3 CE Requirements 

To make an MT-600/8000 comply with EMC directives, and to reduce susceptibility to electrical 

interference, a separate #14 AWG ground wire should be taken to the chassis ground terminal of the 

power connector. This ground connection should be run directly to the central star earth connection 

point (as recommended in most Installation Instructions). 

2.2.4 Safety Guidelines 

This section presents recommended installation practices, and procedures. Since no two 

applications are identical, these recommendations should be considered as guidelines. 

 

Hardware 
Considerations 

WARNING! 

The system designer should be aware that devices in Controller systems could 
fail and thereby create an unsafe condition. Furthermore, electrical 
interference in an operator interface, such as an MT-600/8000, can lead to 
equipment start-up, which could result in property damage and/or physical 
injury to the equipment operator. 

If you, or your company, use any programmable control systems that require 
an operator or attendant, you should be aware that this potential safety hazard 
exists and take appropriate precautions. Although the specific design steps 
depend on your particular application, the following precautions generally 
apply to installation of solid-state programmable control devices. In addition, 
these precautions conform to the guidelines for installation of Controllers as 
recommended in the NEMA ICS 3-304 Control Standards. 

Programming 
Considerations 

To conform with ICS Safety Recommendations, checks should be placed 

Содержание MT-610 Series

Страница 1: ...0 Series has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper wire routing and grounding will insure proper operation Mechanical Environment Avoid installing units in environments where severe mechanical vibration or shocks are present 2 0 Installation...

Страница 2: ...ent This will cause condensation of water in the device z Do not install these terminals in environments where have inflammable gases 2 2 Power Connections Make sure that all local and national electrical standards are met when the installing the unit Contact your local authorities to determine which codes apply 2 2 1 Power Requirements Power The MT 610X 8104X can be powered by DC power only The s...

Страница 3: ...ected to a tree from a central star earth ground point This ensures that no ground conductor carries current from any other branch 2 2 3 CE Requirements To make an MT 600 8000 comply with EMC directives and to reduce susceptibility to electrical interference a separate 14 AWG ground wire should be taken to the chassis ground terminal of the power connector This ground connection should be run dire...

Страница 4: ... authorized personnel can make such changes These recommendations are intended as safeguards against the failure of critical components and the effects of such failures or the inadvertent errors that might be introduced if programs are changed while the equipment is in operation z The ICS 3 304 81 Safety Recommendations are reproduced by permission of the National Electrical Manufacturers Associat...

Страница 5: ...n assignment of the 9 Pin Male SUB D COM1 RS 232 and COM2 RS 232 Port Pin Designations COM1 RS 232 COM2 RS 232 Pin Symbol COM1 RS232 COM2 RS232 1 Not used 2 RxD Received Data 3 TxD Transmitted Data 4 TxD Transmitted Data 5 GND Signal Ground 6 RxD Received Data 7 RTS Ready to send output 8 CTS Clear to send input 9 Not used 2 4 2 Connector COM1 RS485 COM3 RS485 and COM3 RS232 The 9 Pin Female SUB D...

Страница 6: ...r Wire MT8 Ethernet RZC045120 Direct connect Ethernet crossover cable MT8000 Ethernet RJ45 Wire color PC or Note Book RJ45 1 TX White Orange 3 RX 2 TX Orange 6 RX 3 RX White Green 1 TX 6 RX Green 2 TX MT8 COM1 RZC002320 1 5 6 9 5 9 1 6 6 9 1 5 MT8 COM3 RZC004850 5 9 1 6 1 5 6 9 1 5 6 9 5 9 1 6 ...

Страница 7: ...cd m 2 Color 65 536 colors Contrast Ratio 300 1 Resolution WxH dots 640 x 480 Back light CCFLx2 CCFL life time 40 000 hr min Touch panel 4 wires resistive type Touch Accuracy 2mm Surface Hardness 4H I O port COM1 RS 232 RS 485 2W 4W COM2 RS232 COM3 RS 232 RS 4852W 1 Ethernet port 10 100 Base T SD CARD SLOT PS 2 Port Connector USB Host 2 USB Host port Audio 1 x Audio Line Out 1 x MIC In Processor A...

Страница 8: ...28 43mm 1 69 COM1 RS232 COM2 RS232 COM3 RS485 COM3 RS232 COM1 RS485 2 4W SD PS 2 b a e f l m k j i h g g g g c d 50mm 1 97 A N A H SD CARD SLOT B IDE Interface DOM Slot I Com1 RS232 Com2 RS232 C Line Out J Com1 RS485 Com3 RS485 Com3 RS232 D Mic In K Ethernet Port 10 100 Base T E Fuse Reset Button L USB Host Port x 2 F Power Connector M PS 2 Port Connector G VESA 75mm Screw Holes Cutout Dimensions ...

Отзывы: