![weintek iR-ETN Скачать руководство пользователя страница 8](http://html.mh-extra.com/html/weintek/ir-etn/ir-etn_user-manual_953138008.webp)
iR-ETN User Manual
5
0~511
0000~
01FF
Write
5,15
864~927
0360~
039F
Write
6,16,23
Register Mapping
7.2
Parameter
Start address
Read/Write
Function Code
Dec
Hex
Analog Input
0~255
0000~
00FF
Read
3,4,23
Analog Output
256~511
0100~
01FF
Read
3,23
Write
6,16,23
Registers
----------
Read
3,4,23
---------
Write
6,16,23
TCP/IP Register
7.3
Address
Read/Write
Data Size
Description
Dec
Hex
1000
03E8
Read
3word
(MAC-address).Ethernet physical address
If 00-0C-26-01-02-03, then 0x000C, 0x2601, 0x0203.
1003
03EB
Read/Write
2word
IP address
if 192.168.0.212, then 0xC0A8, 0x00D4.
1005
03ED
Read/Write
2word
subnet mask
if 255.255.255.0, then 0xFFFF, 0xFF00
1011
03F3
Read
1word
Number of TCP/IP connections
*TCP/IP Register Settings will take effect after cold reset or after giving Device Reset
Warm command.
Device Information Register
7.4
Address
Read/Write
Data size
Description
Dec
Hex
3000
0BB8
Read
4word
Vendor name string 8 char: “weintek” (ASCII)
3004
0BBC
Read
1word
Product Code of iR-ETN is 0x0702
3005
0BBD
Read
1word
Firmware revision V1.23.4, 0x1234
3006
0BBE
Read
1word
Hardware revision V1.23.4, 0x1234
3007
0BBF
Read
1word
Power consumption unit mW
3008-
3023
0BC0-
0BCF
R/W
16word
Product name, default=“iR-ETN” (ASCII)
iBus Information Register
7.5
Address
Read/Write
Data size
Description
Dec
Hex
10000
2710
Read
1word
Slot 0 Product code (iR-ETN)
10001
2711
Read
1word
Slot 1 Module Product code
10001~
10016
2712~
2720
Read
1word
Slot 2~Slot 16 Module Product code