Click the System Settings button and configure 

cMT-SVR.

 

The interface can be used to download or upload 
project files. 

 

 

 

EasyBuilder Pro Software Settings

 

Launch EasyBuilder Pro software, select your   
project file, press F7 shortcut key to open 
the download dialog box:   

 
Select Ethernet > IP tab > Enter your cMT-SVR 
IP > Click Download to download this project   
file to cMT-SVR. 

 
( Please refer to EasyBuilder Pro User Manual 
  for software operation details ) 
 

Communication Connections 

COM1 [RS232] 

 

 

 

 

 

 

 

 

DIP SW Settings 

When SW1 is turned ON and power the   
unit again, the IP setting is restored to 
default: 
Ethernet 1: DHCP 
Ethernet 2: 192.168.100.1 
 
When restore factory default, the projects 
and data stored in the unit are all cleared. 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION

NN

 

 

Limited Warranty                                                                                                         

 

This product is limited warranted against defects in design and manufacture. The proven 

defective product will either be repaired or replaced, at Weintek’s discretion. This warranty 

shall not cover any product which is   

(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products. 
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.   
(c) Product has been repaired or taken apart by unauthorized technicians.   
(d) Products whose identification markings have been removed or damaged.

 

 
 

NOTE:   

Make sure that all local and national electrical standards are met when installing 
the unit. Contact your local authorities to determine which codes apply. 

PIN# 

Symbol 

COM1 

[RS-232] 

COM2 [RS-485] 

COM3 

[RS-485 

2W] 

2W 

4W 

Data+ 

 

 

 

Data+ 

RxD 

Received Data 

 

 

 

TxD 

Transmitted Data 

 

 

 

Data- 

 

 

 

Data- 

GND 

Signal Ground 

Rx+ 

 

Data+ 

Rx+ 

 

Rx- 

 

Data- 

Rx- 

 

Tx+ 

 

 

Tx+ 

 

Tx- 

 

 

Tx- 

 

 

SW1 

SW2 

Mode 

OFF

 

OFF 

Normal Mode 

ON

 

OFF

 

Restore Ethernet IP Settings 

OFF 

ON

 

Boot Loader Mode 

ON

 

ON 

Restore Factory Default 

 

CAUTION 

NOTE: 

Make sure that all local and national electrical standards are met when 

installing the unit. Contact your local authorities to determine which codes apply. 

Hardware 
Considerations 

The system designer should be aware that devices in Controller systems could fail and thereby 

create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to 

equipment start-up, which could result in property damage and/or physical injury to the operator. 

If you use any programmable control systems that require an operator, be aware that this potential 

safety hazard exists and take appropriate precautions. Although the specific design steps depend on 

your particular application, the following precautions generally apply to installation of solid-state 

programmable control devices, and conform to the guidelines for installation of Controllers 

recommended in NEMA ICS 3-304 Control Standards.

 

Programming 
Considerations 

To conform with ICS Safety Recommendations, checks should be placed in the controller to ensure 

that all writable registers that control critical parts of plant or machinery have limit checks built into 

the program, with an out-of-limit safe shut down procedure to ensure safety of personnel. 

 

GMECSVR00_cMT_SVR_Installation_130722 

 

 

 

 

 

 

 

 

DANGER 

Power 

The unit can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with 

most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a 

switching power supply. The peak starting current can be as high as 500mA.

 

High 
Voltage 

DC voltage sources should provide proper isolation from main AC power and similar hazards. 

Emergency 
Stop 

A Hard-wired EMERGENCY STOP should be fitted in any system using cMT-SVR to comply with 

ICS Safety Recommendations. 

Supply 
Voltage 
Condition 

Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same 

power supply. Note: The 24 VDC output from some controllers may not have enough current to 

power the unit. 

Wire 
Routing 

a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded). 

b. Please use twisted pair cables for power wire and signal wire and conform to the impedance 

matching. 

c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices. 

d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires. 

e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power 

supply and the frame ground. This provides a path for static and high frequency dissipation. 

Typical values to use are 1M Ohm and 4700pF. 

 