EasyBuilder Pro Software Settings

 

Launch EasyBuilder Pro software, select your 
project file, press F7 shortcut key to open the 
download dialog box: Select Ethernet > HMI Name 
tab > Select your cMT-G05 > Click Download to 
download this project file to cMT-G05. 
(Please refer to EasyBuilder Pro User Manual for 
software operation details) 

 

Communication Connection 

NOTE: COM2 and COM3 [RS485] support MPI 
187.5K, please use one at a time

.

 

 

9 Pin, Male, D-sub 
COM1 [RS232] 
COM2 [RS485] 
COM3 [RS485] 

 

 

 

 

 

DIP SW Settings 

Turn ON SW1 and power the   
unit again, the IP setting is restored to 
default: 
Ethernet 1: DHCP 
Ethernet 2: 192.168.100.1 
 
When restore factory default, the projects 
and data stored in the unit are all cleared. 

 

 

Battery Replacement

 

Battery Specification: UL Certification Battery, Type CR1220, Rated 3V, Max. Abnormal Charging Current 
10mA, Working Temperature: max. 70°C 
Battery replacement shall be performed by qualified personnel (engineer) only and care must be taken 
when handling lithium batteries. For more information on battery replacement and disposal considerations, 
please refer to the following link: 

http://www.weintek.com/download/MT8000/eng/FAQ/FAQ_103_Replace_Battery_en.pdf 

   

NOTE: 

Make  sure  that  all  local  and  national  electrical  standards  are  met  when 

installing the unit. Contact your local authorities to determine which codes apply.

 

 

Power

 

Use power output that meets SELV (Safety Extra-Low Voltage) requirements. The unit can be 

powered  by  DC  power  only,  voltage  range:  24

±

20%,  compatible  with  most  controller  DC 

systems. The power conditioning circuitry inside the unit is accomplished by a switching power 

supply. The peak starting current can be as high as 500mA. 

 

Fusing Require- 
ments 

If the Power LED  does  not light up immediately  after power up,  remove power. A  resettable 

fuse will protect against overcurrent faults in DC circuit and the resetting will take place after a 

period of time. Check wiring for proper connections and try to power up again.   

 

High Voltage

 

A  resettable  fuse  will  prevent  damage  for  overcurrent 

condition  however  it  isn’t  guaranteed. 

DC voltage sources should provide proper isolation from main AC power and similar hazards. 

 

Emergency Stop

 

A Hard-wired EMERGENCY STOP should be fitted in any system using an HMI to comply with 

ICS Safety Recommendations. 

 

Supply Voltage 
Condition

 

Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same 

power supply. Note: The 24 VDC output from some controllers may not have enough current to 

power the unit.

 

 

Wire Routing

 

a.  Power wire length should be minimized (Max: 500m shielded, 300m unshielded). 

b.  Please use twisted pair cables for power wire and signal wire and conform to the 

impedance matching. 

c.  If wiring is to be exposed to lightning or surges, use appropriate surge suppression 

devices. 

d.  Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires. 

e.

  Add a resistor and capacitor in the parallel connection between the ungrounded DC power 

supply and the frame ground. This provides a path for static and high frequency 

dissipation. Typical values to use are 1M Ohm and 4700pF

 

   

 

Hardware 
Considerations

 

The  system  designer  should  be  aware  that  devices  in  Controller  systems  could  fail  and 

thereby  create  an  unsafe  condition.  Furthermore,  electrical  interference  in  an  operator 

interface  can  lead  to  equipment  start-up,  which  could  result  in  property  damage  and/or 

physical injury to the operator. 

If  you  use  any  programmable  control  systems  that  require  an  operator,  be  aware  that  this 

potential safety hazard exists and take appropriate precautions. Although the specific design 

steps  depend  on  your  particular  application,  the  following  precautions  generally  apply  to 

installation  of  solid-state  programmable  control  devices,  and  conform  to  the  guidelines  for 

installation of Controllers recommended in NEMA ICS 3-304 Control Standards.

 

 

Programming 
Considerations

 

To conform  with  ICS Safety  Recommendations, checks should be placed in  the controller to 

ensure  that  all  writable  registers  that  control  critical  parts  of  plant  or  machinery  have  limit 

checks built into the program, with an out-of-limit safe shut down procedure to ensure safety of 

personnel. 

GMECMG500_cMT_G05_Installation_200306

 

 

 

 

DANGER 

 

CAUTION 

CAUTION

NN

 

 

Limited Warranty                                                                                                         

 

This product is limited warranted against defects in design and manufacture. The proven 

defective product will either 

be repaired or replaced, at Weintek’s discretion. This warranty 

shall not cover any product which is   

(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products. 
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.   
(c) Product has been repaired or taken apart by unauthorized technicians.   
(d) Products whose identification markings have been removed or damaged.

 

 

NOTE:   

Make sure that all local and national electrical standards are met when installing 
the unit. Contact your local authorities to determine which codes apply. 

PIN# 

COM1 

[RS-232] 

COM2 [RS-485] 

COM3 

[RS-485] 

  2W 

2W 

4W 

 

 

 

Data+ 

RxD 

 

 

 

TxD 

 

 

 

 

 

 

Data- 

GND 

 

Data+ 

Rx+ 

 

 

Data- 

Rx- 

 

 

 

Tx+ 

 

 

 

Tx- 

 

 

SW1 

SW2 

Mode 

OFF

 

OFF 

Normal Mode 

ON

 

OFF

 

Restore Ethernet IP Settings 

OFF 

ON

 

Boot Loader Mode 

ON

 

ON 

Restore Factory Default 

 

CAUTION

NN

 

 

NOTE:   

Make sure that all local and national electrical standards are met when installing 
the unit. Contact your local authorities to determine which codes apply. 