Installation and Startup Guide
This document covers the installation of cMT-G05, for the detailed specifications and operation, please
refer to Datasheet, Brochure and EasyBuilder Pro User Manual. Please read all warnings, precautions, and
instructions on the device carefully before use.
Install Environment:
Electrical
Environment
The HMI product has been tested to conform to European CE requirements. This
means that the circuitry is designed to resist the effects of electrical noise. This
does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
Environmental
Considerations
(1) Make sure that the units are installed correctly and that the operating limits
are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2) Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) Conform to UL 61010-2-201 safety requirement for use in Pollution Degree
2 Environment and dry location.
(6) Relative Humidity: 10% ~ 90% (non-condensing)
Cleaning
Considerations
Clean the device using dry cloths. Do not use liquid or spray detergents for
cleaning.
IP rating
IP 20
Warning
Protection impairment if used in a manner not specified by the manufacturer.
Déficit de protection si utilisé d'une manière non spécifiée par le fabricant.
Unpacking the Unit
Unpack and check the delivery. If damage is found, notify the supplier.
NOTE: Place the unit on a stable surface during installation. Dropping it or letting it fall may cause
damage.
(1) Installation Instruction, A4 double sided *1
(2) Power Connector *1
(3) cMT-G05 *1
Installation Instructions
Rail mounting: DIN rail 35mm
Panel mounting: Use two M4 or #8 panhead screws, mounting hole size is 4.6mm
Plan for adequate space around the unit and inside the enclosure, for ventilation and cables. Consider the
heat from other devices inside the enclosure. The ambient temperature around the unit must be -20 ~ 55°C
Power Connections
Power Connector Specifications:
Wire AWG: 24~12
Wiring Conductor Minimum Temperature: 75°C
Screw Torque: 4.5 lbf-in (max.)
Copper conduct only.
Spécifications du connecteur d'alimentation:
AWG de fil: 24 ~ 12
Température minimale du conducteur de câblage: 75°C
Couple de vis: 4.5 lbf-in (max.)
Conducteur en cuivre seulement
NOTE: Connect posi
tive DC line to the ‘+’ terminal and the DC
ground to the ‘-’ terminal.
System Settings
Connect cMT-G05 with a router using a RJ-45 cable, launch EasyBuilder Pro on your computer, open
Download window as shown in part 6 in this document to find this cMT-G05.
After connecting cMT-G05 successfully, enter the IP address of this cMT-G05 in the browser to open the
System Settings page, and then enter
the default password “111111” to log in and configure cMT-G05.
cMT-G05
Installation Instruction
3
5
4
1
2