background image

SlimFit

 Series 3

 

 

gas

-

fired

 

water

 

boiler

 — 

Application Guide

Part number SF-E009-A/0516

2

- continued 

•  Stack / Vent Flow Rate for each individual boiler model is listed in the table below. This flow rate is 

based on the unit running at 9.25% CO

2

 and the maximum flue gas temperature of 210°F.  

The values can vary depending on the location of the installation and operating conditions.

•  A carbon monoxide detector(s) is required in the boiler room for 

SlimFit

 boilers installed in a Cat-

egory II configuration. The carbon monoxide detector must be wired on the same electrical circuit as 
the boiler. Check your local codes for any  additional requirements of carbon monoxide detectors.

 

I

mproper Installation of a Category II vent system resulting in positive pressure in the vent system can 

result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.  

   

Weil-McLain recommends the use of a Variable Speed Chimney Fan/ Power venter to ensure that the  

appropriate negative pressure is maintained for Category II venting.  This is recommended because, as a 
result of the boiler’s efficiency, the exhaust gas temperatures can be quite low resulting in less natural draft.  
A flow proving switch should be wired into the Proof of Closure jumper circuit on the boiler control.  See 
the boiler manual for additional information.  The use of this device should be considered in any Engi-
neered Vent system.

  Weil-McLain recommends the use of a Double Acting Barometric Damper or Modulating Damper to en-

sure the appropriate negative pressure range is kept for Category II venting. The use of this device should 
be considered in any Engineered Vent system.

  When using a damper of any kind, it is recommended to use a thermal spill switch to detect any exhaust 

flow into the boiler room. Verify the temperature range on the thermal spill switch is adequate for the Flue 
gas temperature from the 

SlimFit

 boiler. The use and set-point of this shall be determined by the system 

designer. The Auto reset input on the Boiler’s control can be used to wire in the thermal spill switch.

  The thermal spill switch should shut down all boilers connected to the common flue. Each boiler must be 

wired to its own set of dry contacts activated by the spill switch.

  Increasing the negative pressure in the vent pipe will slightly increase the firing rate at low fire, thus reduc-

ing the boiler’s true modulation range. Consider this factor during system design.

Code Compliance 

 

Venting / Combustion air piping – Installations must provide provisions for combustion and 
ventilation air in accordance with the section “Venting of Equipment”, of the National Fuel Gas Code, 
ANSI Z223.1 / NFPA 54, or “Venting Systems and Air Supply for appliances” of the Natural Gas and 
Propane Installation Code, CAN/CSA B149.1, or applicable provisions of the local building codes.

TABLE 1

  Rating & Vent Data

Boiler 

Model

Input 

Btuh

Stack / Vent

flow rate  

scfm

Negative Pressure to be  

maintained at 

Vent Connection of the boiler

Inches w.c.

SlimFit Vent

Adapter  

required for 

Category II

SF 550

550,000

128

-0.001 to -0.100

6”- 8”

SF 750

750,000

175

-0.001 to -0.100

6”- 8”

Отзывы: