background image

Part No. 

SF-E009-A/0516

Application Guide

for 

Common Venting SlimFit 550-750 Series 3 Boilers

Hazard definitions

The following defined terms are used throughout these Instructions to bring attention to the presence of hazards of 

various risk levels or to important information concerning the life of the product.

 

Indicates presence of hazards that can cause severe personal injury, death or substantial property damage.

 

Indicates special instructions on installation, operation or maintenance that are important but not related 

to personal injury or property damage.

Common Venting methods and requirements for SlimFit Boilers (SF 550 and SF 750 Series 3)

The 

SlimFit

 boiler can be common vented when the following requirements are met. 

•  Common venting of the 

SlimFit

 boiler can only be done in a Category II vent system. All require-

ments for the 

SlimFit

 boiler to be vented in a Category II configuration must be met as stated in the 

SlimFit

 Boiler Manual or all subsequent addendas.

• 

SlimFit

 boilers can only be common vented with other 

SlimFit

 Boilers.  

•  The maximum number of 

SlimFit

 boilers to be common vented together is eight.  

•  The Vent system for a Category II 

SlimFit

 boiler is considered a Designed / Engineered vent system 

and should be designed by a professional using accepted engineering practices. 

•  Vertical Vent only.
•  Combustion air must come from the boiler room. See Direct Exhaust – Combustion Air opening 

requirements in 

SlimFit

 Vent Category II Addendum.

•  Must increase venting to 6”or 8” using a 8” to 6” bell reducer at boiler vent adapter for Category II 

Vent Connection.

•  The Vent System should be designed so that the pressure in the vertical vent pipe is between the 

ranges provided in the Table 1, page 2, during all operating conditions (i.e., High Fire through Low 
Fire, prepurge, post purge and ignition). If a negative pressure cannot be guaranteed at prepurge and 
post purge, a backflow preventer is required on each boiler’s vent.

 

To prevent backflow through boiler, negative pressure must be maintained in vent system at all 
times including prepurge and post purge cycles.

•  Flue gas temperature should not exceed 210°F; the boiler will shut down and recycle if it does. The 

flue gas temperature should typically be within 20°F of the return water temperature of the boiler. If 
there is the potential for a wide variation in return water temperatures, the lowest possible tempera-
ture should be used for any calculations.  

- continued on next page

®

Series 3

 

Models 550 and 750 MBH

Commercial Condensing

Gas-fired water boilers

Отзывы: