Service periodically . . . . . . . . . . . . 

Figure 7

  Float type low water cutoff

Figure 8

  Probe type low water cutoff

Probe type— See Figure 8

1.  Clean probe type low water cutoff for proper 

operation.

a.  Turn off power to boiler and wait 5 minutes.

b.  Drain water to bottom of gauge glass.

c.  Turn on power.

d.  Set thermostat to call for heat. Red neon lamp 

on lower water cutoff should light.

e.  Wait 5 minutes. Boiler should not fire.

f.  Refill boiler to correct water line. Red lamp 

should go off.

g.  Wait 5 minutes. Boiler should fire.

h.  Return thermostat to normal setting.

Test low water cutoff (all steam boilers) 

(water boilers, if installed)

If the system is equipped with a low water cutoff, test the low water cutoff periodically during the heating season.

2.  Check float type low water cutoff for proper 

operation.

a.  Turn operating control to call for heat.
b.  Before water gets hot, drain to bottom of gauge 

glass.  Boiler should shut off after water level 
lowers a few inches.

c.  Refill boiler to correct waterline. Boiler should 

come back on.

.

 

Boiler pressure and temperature must be low to avoid 

the potential of severe burns from steam or hot water.

Float type — See Figure 7

1.  Clean float type low water cutoff to clear float 

chamber of sediment.

a.  Open blowdown valve at bottom control.
b.  Drain water into a bucket.

Содержание PEG 5 Series

Страница 1: ...fire department Installation and service must be performed by a qualified installer service technician or the gas supplier If the information in this manual is not followed exactly a fire or explosion...

Страница 2: ...sonal injury death or substantial property damage Indicates presence of hazards that can cause severe personal injury death or substantial property damage Indicates presence of hazards that will or ca...

Страница 3: ...ler or piping must be repaired at once to prevent makeup water Do not add cold water to hot boiler Thermal shock can cause sections to crack Boiler operation Do not block flow of combustion or ventila...

Страница 4: ...fold orifices 5 Control module 6 Inducer CGi only 7 Vent damper CGa only 8 Water temperature sensor 9 Transformer 10 Spill switch CGa only 11 Air pressure switch CGi only 12 Rollout thermal fuse eleme...

Страница 5: ...burner 3 Main burner 4 Gas manifold orifices 5 Control module 7 Vent damper 9 Transformer 10 Spill switch 12 Rollout thermal fuse element 13 Low water cutoff steam boilers 14 Limit control s 15 Draft...

Страница 6: ...only by a qualified service technician Owner maintenance see following pages for instructions A nnual start up Inspect Reported problems Boiler area Air openings Flue gas vent system Pilot and main b...

Страница 7: ...echnician to inspect the boiler and vent system for possible damage from acid corrosion If products cannot be removed immediately call a qualified service technician to install an outside combustion a...

Страница 8: ...ators relief valve and other fittings Immediately call a qualified service technician to repair any leaks 1 Visually inspect all parts or the flue gas venting system for any signs of blockage leakage...

Страница 9: ...ot flame sensor spark ignited pilot 3 Thermocouple or thermopile or pilot flame sensor glowing cherry red Improper pilot flame 1 Overfired Large flame lifting or blowing past pilot flame sensor 2 Unde...

Страница 10: ...turn thermostat to normal setting Test low water cutoff all steam boilers water boilers if installed If the system is equipped with a low water cutoff test the low water cutoff periodically during the...

Страница 11: ...to clean the valve seat If the valve continues to weep afterwards contact your qualified service technician to inspect the valve and system 5 If water does not flow from the valve when you lift the le...

Страница 12: ...tempt to light the pilot Use caution when attempting to light the propane pilot This should be done by a qualified service technician particularly if pilot outages are common Periodically check the od...

Страница 13: ...tat to lowest setting 3 Turn off all electrical power to the appliance 4 Remove from panel 5 This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light...

Страница 14: ...at to lowest setting 3 Turn off all electrical power to the appliance 4 Remove front panel 5 This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light...

Страница 15: ...wer to the appliance 4 Remove front panel 5 This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light the pilot by hand 6 Depress gas control knob sli...

Страница 16: ...CGa CGi EG EGH LGB PEG Boilers 16 Part Number 550 142 801 1112 Operating instructions Spark ignited pilot Gas valve Robertshaw 7200 CGa 25 to CGa 6 EG 30 to EG 50 PEG 30 to PEG 50...

Страница 17: ...User s Information Manual 17 Part Number 550 142 801 1112 Operating instructions Spark ignited pilot Gas valve Robertshaw 7000DERHC EGH 85 to EGH 125...

Страница 18: ...the thermostat to lowest setting 3 Turn off all electrical power to the appliance 4 Remove jacket front panel 5 This appliance is equipped with an ignition device which automatically lights the burner...

Страница 19: ...User s Information Manual 19 Part Number 550 142 801 1112 Operating instructions Spark ignited pilot LGB...

Страница 20: ...se stop leak compounds Black water condition Oxygen corrosion due to leaks in boiler and piping Have qualified service technician repair at once Keep pH of water between 7 0 to 8 5 Popping or percolat...

Отзывы: