GOLD CGa Gas-Fired Water Boiler — Boiler Manual
Start-up — if boiler doesn’t start . . .
6c
Check for:
%LIMINATE ALL SYSTEM LEAKS
#ONTINUAL FRESH MAKEUP WATER
will reduce boiler life. Minerals
can build up in sections, reduc-
ing heat transfer, overheating
cast iron, and causing section
failure.
If you discover evidence of any
gas leak, shut down the boiler
at once. Find the leak source
with bubble test and repair im-
MEDIATELY $O NOT START BOILER
again until corrected. Failure to
comply could result in severe
personal injury, death or sub-
stantial property damage.
$O NOT USE
PETROLEUMBASED
CLEANINGORSEALINGCOMPOUNDS
in boiler system. Severe damage
to boiler will occur, resulting in
substantial property damage.
'ASNOTTURNEDONATMETERORBOILER
5. Incoming gas pressure less than:
vWCFORNATURALGASvWCFORPROPANEGAS
6. If none of the above corrects the problem, refer to
4ROUBLESHOOT
ing
,
Section
of this manual.
1. Loose connections, blown fuse or
SERVICESWITCHOFF
(IGHLIMITSWITCHSETBELOWBOILER
WATERTEMPERATURE
3. Thermostat set below room tem-
PERATURE
Start-up — operate boiler
(continued)
6b
Start the boiler
s &OLLOWTHE
,IGHTING/PERATING)NSTRUCTIONS
from
3ECTION OR
to start the boiler. Remove boiler
jacket door and note the gas valve manufacturer
and model number. Use only the lighting/operat-
ing instruction which applies to this gas valve (see
4ABLE
, page 30). (The lighting instruction label on
the boiler provides the same information.)
s 3EE
3ECTIONC
if boiler fails to start.
Check system and boiler
1.
#HECK SYSTEM PIPING FOR LEAKS
If found, shut
down boiler and repair immediately.
2.
6ENTAIRFROMSYSTEM
using manual vents. Air in
the system will interfere with circulation and cause
heat distribution problems and noise.
3.
)NSPECT VENT SYSTEM
thoroughly for signs of
deterioration from corrosion, physical damage or
SAGGING6ERIFYTHATMASONRYCHIMNEYLINERSAREIN
good condition, with no obstructions, and there are
no openings into the chimney.
4.
#HECKAROUNDTHEBOILER
for gas odor following the
procedure of Section
A
of this manual.
5.
6ERIFYOPERATION
per Section
D
. Perform check-out
procedure in Section
and fill in the
)NSTALLATION
ANDSERVICECERTIlCATE
on the same page.