background image

Table 1:   Course adjustment settings—Throttle and offset 

adjustments to be made prior to first ignition, by 

size. 

 

Boiler 

Model 

Throttle Turns 

(Counterclockwise 

from Bottom-out 

Position) 

Offset Turns 

(Counterclockwise 

from Factory NG 

Position) 

220 LP 

3/4 

1/4 

299 LP 

1-3/8 

1/4 

399 LP 

1-5/8 

1/4 

 

Before firing, verify that the “Max Rate” for the input 

(priority) used to fire the boiler is set between 96% and 

100%.  Also verify that the ‘Min Rate” is set to 10% or the 

minimum rate allowed (if above 2000 ft. elevation).  

Adjust control settings if not at proper rate.  Verify that 

boiler is operating at the expected firing rate at both 

high- and low-fire during combustion analysis.  Refer to 

Table 2 for proper low-fire rate based on altitude settings. 

 

  During combustion analysis, ensure boiler is 

operating at the expected firing rate.  Failure 

to operate boiler at proper rate during 

combustion testing and adjustment could 

result in incorrect combustion settings. 

Improper gas valve settings can cause 

severe personal injury, death or property 

damage. 

 

Table 2:   Low-fire blower speeds—Minimum blower 

speed settings according to altitude settings. 

 

Altitude 

Setting (ft.) 

Lowest Rate for Altitude 

220 

299 

399 

0-2000 

10% 

10% 

10% 

2500 

11% 

11% 

12% 

3000 

12% 

11% 

12% 

3500 

12% 

11% 

12% 

4000 

12% 

12% 

13% 

4500 

13% 

12% 

13% 

5000 

13% 

12% 

13% 

5500 

13% 

13% 

14% 

6000 

14% 

13% 

14% 

6500 

14% 

13% 

14% 

7000 

14% 

14% 

15% 

7500 

15% 

14% 

15% 

8000 

15% 

14% 

16% 

8500 

15% 

14% 

16% 

9000 

16% 

15% 

16% 

9500 

16% 

15% 

17% 

10000 

17% 

15% 

17% 

10500 

17% 

16% 

17% 

11000 

17% 

16% 

18% 

 

Review the procedure and control sequence for the 

operation of the Manual Test Mode in the section of the 

boiler manual “Manual Test Mode for Single and Multiple 

Boilers”.  The procedure differs between boilers set as a 

single or multiple-boiler unit. 

 

Do NOT allow the boiler to modulate freely until the 

combustion analysis and adjustment is complete.  Fire 

the boiler and force it to High Fire in Manual Test Mode. 

Adjust the high fire combustion first, using the throttle 

adjustment screw, to the specification in the boiler 

manual, reproduced in Table 3.  Then, force the boiler to 

low fire and adjust the offset regulating screw to the 

specification in the boiler manual, reproduced in Table 3. 

Follow the full startup instructions found in the Evergreen 

Boiler Manual.  

 

Table 3:   Acceptable combustion values—measured 

values must be within the ranges given below. 

 

Boiler 

Model 

High Fire 

Low Fire 

% CO2 

CO 

ppm 

% CO2 

CO ppm 

220 LP  10.75 ±0.50 

< 120 

10.25 ±0.50 

< 50 

299 LP  10.75 ±0.50 

< 120 

10.25 ±0.50 

< 50 

399 LP  10.75 ±0.50 

< 120 

10.25 ±0.50 

< 50 

 

 

To clarify, both the high fire and low fire gas adjustment 

MUST be made with a properly working, calibrated 

combustion analyzer according to the instructions in the 

boiler manual to ensure safe, reliable operation. 

 

The coarse adjustment prescribed by this bulletin should 

result in combustion settings that allow for ignition and 

are a starting point for further adjustment.  If, after 

following the procedure above, the boiler will not ignite 

or, during combustion analysis, the analyzer reads less 

than 1.0% O

2

, contact Weil-McLain Technical Services for 

assistance. 

Отзывы: