Weil-McLain Technical Bulletin 

TB1601 - February 15, 2016 

 

 

 

  

 Evergreen Liquid Propane Conversion – Gas Valve Adjustment   

 

Hazard Definitions: 

The following defined terms are used throughout this manual to bring attention to the presence of hazards of 

various risk levels or to important information concerning the life of the product. 

 

 Indicates presence of hazards that 

will cause severe personal injury, 

death or substantial property 

damage. 

 
Indicates presence of hazards that 

can cause severe personal injury, 

death or substantial property damage. 

 

  The use of a properly working, calibrated 

flue gas analyzer is required to convert this 

unit and determine proper gas valve 

settings. Do not perform this conversion 

without a flue gas analyzer. Improper gas 

valve settings can cause severe personal 

injury, death or property damage. 

 

   Do NOT fire the Evergreen™ boiler after the 

Liquid Propane conversion without utilizing a 

properly working, calibrated combustion 

analyzer to adjust the gas valve to the 

proper settings after the initial light off.  Do 

NOT allow the boiler to modulate freely until 

the combustion analysis and adjustment is 

complete.  Failure to do so may result in a 

loud ignition that may cause burner/boiler 

damage.  Please refer to the Evergreen LP 

conversion instructions for the proper LP 

conversion procedure.  Failure to follow all 

directions may cause boiler damage and 

could result in severe personal injury, death 

or substantial property damage. 

 

This technical bulletin describes the proper initial, coarse 

adjustment of the Evergreen gas valve for LP operation.  

This adjustment must be made prior to initially lighting the 

LP gas boiler.  Refer to the boiler manual for instructions 

and figures related to gas valve adjustment.  Figure 1 is 

included in this bulletin as a reference of throttle and 

offset locations. 

 

Prior to the boiler’s first ignition, adjust the throttle 

adjustment screw by first turning the screw clockwise until 

it bottoms out – do not apply any torque.  Adjust the 

throttle screw in a counterclockwise direction with 

precisely the number of turns listed in Table 1, according 

to the boiler model/size.   

 

After the throttle has been adjusted coarsely, the offset 

regulating screw must be adjusted.  Remove the sealed, 

slotted cap protecting the white offset regulating screw 

before making adjustments. It is critical to be precise for 

the adjustment of the offset regulating screw.  

 

Figure 1  Gas valve adjustment locations—ONLY for use 

by a qualified technician, using properly 

working, calibrated combustion test 

instruments. 

 

 

Do NOT attempt to bottom out the offset regulating 

screw as was done for the throttle adjustment.  

Adjustments to the offset regulating screw should be 

made from the factory-provided natural gas position.  

Adjust the offset regulating screw using the following 

steps, referencing Figure 2: 

 

1.

 

Use a marker to mark the corner of one tip of the 

cross on the offset regulating screw and the 

corresponding location on the outside of the screw 

housing, as shown in Figure 2a. 

2.

 

Turn the offset regulating screw 1/4 turn 

counterclockwise, ensuring that the tip of the cross 

aligns with the mark on the outside of the screw 

housing, as shown in Figure 2b. 

 

Figure 2  Offset regulating screw adjustment—(a) 

Marking factory-provided NG position. (b) View 

after 1/4 turn CCW adjustment. 

 
 

a)

 

 

b) 

 

 

 

 

 