Port openings must be of captured seal design – a machined groove assures uniform 
compression of the sealing ring and protects the seal from contaminants. Elastomer 
sealing rings are to be used to provide permanent watertight seal between sections. 
Unlike cast iron or steel push nipples, the elasticity of the seals fills any gaps caused 
by misalignment or expansion or contraction. 

 

Shipped with insulated heavy gauge steel jacket(s) with durable powdered paint  

     

enamel finish. Jacket designed to be installed after connecting supply and return 

 

piping.  

Side panels can be removed without tools for easy servicing.

 

 

D. 

Tankless heaters or indirect water heaters 

 

Provide (    ) internal tankless water heater(s) inserted into the left hand side of the 
tankless intermediate (TI) section in the opening provided. Allow 34” minimum 
clearance on left side of boiler for cleaning and servicing. Tankless openings must be 
on same side as the flue passage cleanout plates to minimize space requirements. 

 

E. Boiler 

foundation(s):

 

 

Installer to construct needed support and level concrete foundation(s) where boiler 
room floor is uneven or will not support the weight of the boiler(s). 

 

F. Boiler 

trim: 

1.  All electrical components to be of high quality and bear the U.L. label. 

a)  Water boiler(s) controls furnished: 

1)  Combination low temperature limit (operating) and 

manual reset 

high 

temperature limit control. 

2)  Low temperature limit set according to system design. High temperature limit set 

at least 20

°

F higher than the low limit (240

°

F is the maximum allowable water 

temperature). 

3) Combination 

pressure-temperature gauge with dial clearly marked and easy to 

read.  

4)  ASME certified pressure relief valve, set to relieve at 30 PSIG. Optional relief 

valves available up to and including maximum allowable pressure. Side outlet 
discharge type; contractor to pipe outlet to floor drain or near floor, avoiding any 
area where freezing could occur. 

b)  Steam boiler(s) standard controls furnished: 

1)  Low pressuretrol (operating) and high pressuretrol set at maximum pressure as 

a safety control. 

2)  Steam pressure gauge with dial clearly marked and easy to read. 
3)  Gauge cock water set with gauge glass, guards and aluminum water level plate. 
4)  ASME certified pressure relief valve, set to relieve at 15 PSIG. Side outlet 

discharge type; contractor to pipe outlet to floor drain or near floor, avoiding any 
area where freezing could occur. 

c)  Low water cut-off for water or steam boiler(s): 

1)  Boiler(s) to be furnished with U.L. labeled low water cut-off with ASME working 

pressure rating equal to the ASME rating of the relief valve. 

2)  Do not use quick-connect fittings on boiler(s). 
3)  Install cut-off according to manufacturer’s instructions. 

Содержание 88

Страница 1: ...d and or No 2 fuel oil 5 Water or steam 6 Forced or balanced draft D Boiler s shall have I B R Hydronics Institute gross output s at 100 firing rate MBH per boiler E Boiler s shall be manufactured by ISO 9001 registered company to conform to Section IV of the ASME Boiler and Pressure Vessel Code 1 Individual sections and section assembly to be hydrostatically pressure tested at factory in accordan...

Страница 2: ...ficient tappings to install required controls Limited 10 year warranty against workmanship and defects to be in writing by manufacturer C Boiler s Provided with HXT bars to maximize heat transfer Provided with cast in air elimination to separate air from circulating water Provided with expansion tank tapping to divert separated air to expansion tank Constructed to provide balanced water flow throu...

Страница 3: ... L label a Water boiler s controls furnished 1 Combination low temperature limit operating and manual reset high temperature limit control 2 Low temperature limit set according to system design High temperature limit set at least 20 F higher than the low limit 240 F is the maximum allowable water temperature 3 Combination pressure temperature gauge with dial clearly marked and easy to read 4 ASME ...

Страница 4: ...rner s designed to ensure high efficiency and good performance under forced draft conditions with 0 1 W C positive pressure at the flue collar 8 Burner to be adjusted to provide 9 5 to 10 0 CO2 for gas and or 11 5 to 12 CO2 with zero smoke for oil firing 9 Burner s manufactured by Power Flame Riello Webster Carlin Beckett 10 Burner operating mode on off low high off low high low modulating A Panel...

Отзывы: