![Weidmüller AMS400A Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/weidmuller/ams400a/ams400a_operating-instructions-manual_952254030.webp)
0
•InstrumentSetup
Setupmode
For setup mode, press
AUTO
and
MAN
keys simultaneously. Press
ENT
for password selection or
Å
and
ì
keys for review mode (See below).
Setting
Display
Description
Å
ì
ENT
Password
PASS
Enter password (if you need to change settings).
Note: unit should be out of service
Review Mode/
Skip password
Next
101
Pass word entry (default = 101)
Dec
Inc
Accept
S/W Version
v3.01
S/W Version 3.01 (10 s timeout applies)
-
-
Next
S/W Version
v3.01
S/W Version 3.01
-
-
Next
Displayset-up
Display range
dP=
.
Decimal point position
-
Shift
Next
Accept
dLO=
0.0
Display range lower limit
e.g., 0.0
-
Dec
-
Inc
Next
Accept
dHI=
100.0
Display range Upper limit
e.g., 100.0
-
Dec
-
Inc
Next
Accept
InstallationConfiguration
Installation
Configuration
POP
AA
dA
dd
Input/Output Configuration
‘AA’ Analogue to Analogue
‘dA’ Digital to Analogue
‘dd’ Digital to Digital
-
Dec
-
Inc
Next
Accept
Mode Switch
from Keypad
Enb
Dsb
Allows mode switch from Instrument Keypad
Disables mode switch from instrument Keypad
Toggle
Accept
Configuration
specific
settings
See individual configurations for set-up parameters specific to each type