![Weidmüller 2682350000 Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/weidmuller/2682350000/2682350000_hardware-installation-manual_952360002.webp)
4
5
6 V1.4 / 2022-03-29
Warning / Avertissement
Take into consideration the following guidelines before wiring the device
o
Tenez compte des directrices suivantes avant de câbler l’appareil.
Terminal block is mating with Plug and suitable for 12-24AWG. Torque
value 4.5 lb-in.
o
Le bornier est compatible avec les connecteurs et convient pour 12-
24AWG. Valeur de couple 4,5 lb-in.
The temperature rating of the input connection cable should higher than
105°C.
o
La température de service nominale du câble d’entrée doit être
supérieure à 105 °C.
Supplied by SELV source evaluated by UL 61010-1 or 61010-2-201
power supply only.
o
Fourni par la source SELV évaluée uniquement par l'alimentation UL
61010-1 or 61010-2-201.
Behavior of fault alarm relay (can be triggered by configurable events power
failure or port link down):
Relay contact is closed if the device is powered-off.
Relay contact is open if the device is powered-on and no alarm conditions exist (neither
Power Failure Alarms nor Port Link Loss Alarms are activated (Web menu Warnings
Fault Relay Alarm).
Relay contact closes if any of an activated alarm condition happens.
9. Communication Connections
Switch
IE-SW-AL08M-8GT
is equipped with:
8 x 10/100/1000BASE-T(X) Ethernet ports (Auto MDI-X)
Please only use cables suitable for the respective type of communication and ensure
that signals are protected from possible interference.
9.1
10/100/1000BASE-T(X) RJ45 Ports
The 10/100/1000BASE-T(X) ports located on Ethernet Switch’s front panel are used to
connect to Ethernet-enabled devices. Below we show pinouts for both MDI (NIC-type)
ports and MDI-X (HUB/Switch-type) ports. Auto MDI-X ensures that both wiring-
schemes are supported (Automatic crossover function).
10/100/1000BASE-T(X) RJ45 Pinouts
8-Pin RJ45
Port
10/100BASE-T(X) MDI/MDI-X
1000BASE-T MDI/MDI-X
Pin No.
MDI port
MDI-X port
Pin No.
MDI port
MDI-X port
1
TD+(transmit)
RD+(receive)
1
BI_DA+
BI_DB+
2
TD-(transmit)
RD-(receive)
2
BI_DA-
BI_DB-
3
RD+(receive)
TD+(transmit)
3
BI_DB+
BI_DA+
4
Not used
Not used
4
BI_DC+
BI_DD+
5
Not used
Not used
5
BI_DC-
BI_DD-
6
RD-(receive)
TD-(transmit)
6
BI_DB-
BI_DA-
7
Not used
Not used
7
BI_DD+
BI_DC+
8
Not used
Not used
8
BI_DD-
BI_DC-
9.2
RS232 Console Port
The RS232 Interface with RJ45 connector can be used to access the switch console for
configuration. Additional it can be applied with external Backup/Restore module IE-
EBR-MODULE-RS232-ALM (Article no. 2682610000).
Pinouts Serial
Console Port:
10. User Management
10.1 Device Access (Login to Web Interface)
The Web interface of the Switch can be accessed via following factory default settings:
IP address / Netmask:
192.168.1.110 / 255.255.255.0
User name:
admin
Password:
Detmold
Connect the PC to any Ethernet port of the managed Switch and set the PC’s IP
address to a free one of range 192.168.1.0 / 255.255.255.0
Start a web browser and enter the IP address of the connected Switch into the
browser’s address line (http://192.168.1.110). After the appearance of prompt (login)
enter the login credentials. After confirmation of your input with "OK" the home page of
the switch will be displayed.
10.2 Reset Button (Behavior of Factory Default Settings)
Pressing < 5 seconds: Reboot the switch (Warm Start) and sets IP to Factory
Default IP.
Pressing >= 5 seconds: Resets the switch configuration to Factory Default Settings.
Note: Behavior of reset button can be configured in the Web Interface (Menu Factory Default).
11. LED Indicators
The front panel of the Ethernet Switch contains several LED indicators. The function of
each LED is described in the table below.
LED
Color
Status
Description
PWR1
Green
On
Power is supplied to power input PWR1.
PWR2
Green
On
Power is supplied to power input PWR2.
R-MSTR
(Ring Master)
Green
On
Is Ring Master of an enabled O-Ring.
Ring
Green
On
O-Ring redundancy is enabled.
Blinking
Ring structure is broken (No redundancy).
LNK/ACT
Green
On
Port’s link is active.
Off
Port’s link is inactive.
Blinking
Data is transmitted.
10/100/1000M
Green /
Amber
Green
Port speed is set to 1000 Mbps.
Amber
Port speed is set to 100 Mbps.
Off
Port speed is set to 10 Mbps.
FAULT
Amber
On
Fault Relay indication for Power failure and
Port link loss.
12. Disposal Information
Observe the notes for proper disposal of the
product. You can find the notes here:
www.weidmueller.com/disposal
.
13. Specifications
Technology
Ethernet Standards
IEEE 802.3 for 10BASE-T
IEEE 802.3u for 100BASE-TX
IEEE 802.3z for 1000BASE-X
IEEE 802.3x for flow control
IEEE 802.3az Energy-Efficient Ethernet
IEEE 802.3ad for port trunk with LACP
IEEE 802.1D for STP (Spanning Tree protocol)
IEEE 802.1w for RSTP (Rapid Spanning Tree protocol)
IEEE 802.1s for MSTP (Multiple Spanning Tree Protocol)
IEEE 802.1p for Class of Service
IEEE 802.1Q for VLAN Tagging
IEEE 802.1X for Authentication
IEEE 802.1AB for LLDP (Link Layer Discovery Protocol)
Processing Type
Store and Forward
MAC Table size
8K
Packet buffer size
4 Mbit
Backplane bandwidth
16 Gbps
Jumbo frame support
Up to 9.6 kBytes
Interfaces
RJ45 Ports
10/100/1000BASE-T(X) auto negotiation speed, F/H duplex
mode and auto MDI/MDI-X connection
RS232 Console Port
RS232 Interface with RJ45 connector for Console access and
useable with external Backup/Restore module
LED Indicators
PWR1, PWR2 (Power), Fault (Relay), Ring Master, Ring
Status, Port Link/Activity, Port Full/Half Duplex Mode
Relay Contact
Max. 1A @ 24 V DC for Power Failure and Port Link Loss
Power
Input Voltage
24 V DC (12 - 48 V DC), 2 redundant inputs
Power Consumption (typ.)
13.2 Watts
Connection
One removable 6-pin terminal block, Wiring cable 12-24AWG
Overload Current Protect.
Present
Reverse Polarity Protect.
Present
Physical Characteristics
Housing
IP30 protection, metal
Dimension (W x H x D)
54.3 x 145.1 x 108.3 mm (2.13 x 5.71 x 4.26 inch.)
Weight
779 g
Installation
DIN-rail
Environmental conditions
Operating Temperature
-40 to 75°C (-40 to 167°F)
Storage Temperature
-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity
5 to 95% (non-condensing)
Operating Altitude
Up to 2000 m
Regulatory Approvals
Safety
UL 61010-1; UL 61010-2-201
EMC
EN 55032, EN 55024, FCC Part 15 Subpart B Class A,
IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV,
IEC 61000-4-3 RS: 80 MHz to 1 Ghz: 3 V/m,
IEC 61000-4-4 EFT: Power: 0.5 kV; Signal: 0.5 kV,
IEC 61000-4-5 Surge: Power: 0.5 kV; Signal: 1 kV,
IEC 61000-4-6 CS: 3 Vrms
Shock
IEC 60068-2-27
Free Fall
IEC 60068-2-31
Vibration
IEC 60068-2-6
MTBF
Time
508.672 hrs
Database
Telcordia SR332
Warranty
Time Period
5 years
Contact Information
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26, 32758 Detmold / Germany
Phone +49 (0) 5231 14-0, Fax +49 (0) 5231 14-292083
, Internet