Safety

en

  Safety instructions

The device must only be put into operation and maintained by qualified electricians who are famil

-

iar with national and international laws, provisions and standards.

DANGER

Risk of electric shock

The contacts of the test adapter carry high voltage during the test procedure!

 

Do not use the device near explosive gases, vapours or in a humid environment.

 

Only press the “TEST” button if all 3 slots of the test adapter are occupied (1 test object and 2 

empty enclosures).

CAUTION

Risk from live parts

 

Do not use damaged test leads.

 

First connect the test leads to the test adapter. Then connect the test leads to the device.

 

Never connect the test leads to live cables.

 

Always make sure that all 3 slots of the test adapter are occupied (1 test object and 2 empty en-

closures).

 

Do not insert any foreign objects into the contact sockets of the test adapter.

NOTICE

•  Only use the device for its intended purpose.
• 

The device must not be used if it is damaged or other defects have been identified.

• 

The device must not be opened, modified or converted.

• 

Use only the specified spare parts and accessories.

•  Use only the supplied test leads.
•  Use the test leads only together with the supplied test adapter.
• 

Replace the test adapter (order number 2661050000) if the label is damaged.

The device has double or reinforced insulation in areas where dangerous voltages are present.

The device is supplied with a test adapter. The test adapter is equipped with 3 empty enclosures, 

which serve as placeholders (dummy arresters).

Содержание 2661040000

Страница 1: ...V TEST II SPD component tester Manual...

Страница 2: ......

Страница 3: ...n 17 Time Date screen 18 Display screen 18 Measurement screen 19 Options screen 19 Battery screen 20 MOV screen 20 GDT screen 21 TVS screen 21 Using instrument 22 Power on 22 Power off 22 Restoring fa...

Страница 4: ...ous voltage Danger to life or risk of serious injury Disconnect system and instrument from power supply before beginning work Caution Please follow the documentation This symbol warns of possible dang...

Страница 5: ...e die Messleitungen niemals an spannungsf hrende Leitungen an Achten Sie immer darauf dass alle 3 Steckpl tze des Pr fadapters best ckt sind 1 Pr fling und 2 Leergeh use Stecken Sie keine fremden Gege...

Страница 6: ...ver connect the test leads to live cables Always make sure that all 3 slots of the test adapter are occupied 1 test object and 2 empty en closures Do not insert any foreign objects into the contact so...

Страница 7: ...les fils d essai aux c bles sous tension S assurer toujours que les 3 connecteurs de l adaptateur de test sont occup s 1 l ment tes t et 2 bo tiers vides Ne pas introduire de corps trangers dans les c...

Страница 8: ...l dispositivo Mai collegare i puntali di prova a cavi sotto tensione Assicurarsi sempre che tutte e 3 le fessure dell adattatore di prova siano occupate 1 oggetto da testare e 2 custodie vuote Non ins...

Страница 9: ...a conecte los cables de prueba a cables con carga el ctrica Aseg rese siempre de que las 3 ranuras del adaptador de prueba est n ocupadas 1 objeto de prueba y 2 carcasas vac as No introduzca objetos e...

Страница 10: ...10 2661740000 03 02 2021 Safety zh 3 TEST 1 2 3 1 2 2661050000 3...

Страница 11: ...component can be analyzed as part of an overvoltage protection device The V TEST II is suitable for Weidm ller surge protection devices of the VPU AC series The built in surge protection component is...

Страница 12: ...n stylus This manual 2661740000 If the product is damaged or an item is missing please contact the place of purchase immediately First use It is recommended that battery be fully charged before its us...

Страница 13: ...ng status LED green pulses to indicate instrument is alive 2 Battery status LED blue illuminates when battery is completely flat 1 12 V cell and requires recharging 3 High voltage LED red illuminates...

Страница 14: ...y use and used during firmware update 2 DC power supply input 12 V DC 2000 mA The unit is charged by external power supply refer to Safety section Only use the DC power supply provided 3 Battery compa...

Страница 15: ...ions indicated will be followed refer to Safety section Passcode screen The passcode is used to unlock the instrument to prevent unauthorized use On first use of the instrument before any user options...

Страница 16: ...ether the AC mains is plugged in and whether the instrument is set to Log Measurement mode or not Log screen The Log screen is displayed when the instrument is set to Log Measurement mode This is done...

Страница 17: ...mware is updated this will be reflected in the firmware version shown Change passcode screen The Change passcode screen allows the user to change the passcode required to unlock the instrument on star...

Страница 18: ...me and date settings The condition of this battery is checked each time the instrument is started and the user informed if replacement is required refer to Replacing clock battery section Display scre...

Страница 19: ...be fired three times before the measurement is recorded These settings are retained for when the instrument is next used after a power down Options screen The Options screen is where various user pref...

Страница 20: ...battery icon is color coded to depict the battery condition Gradient green charging Green fully charged Orange needs charging Red flat MOV screen The MOV screen is where the clamp voltage of the MOV...

Страница 21: ...n the Log screen TVS screen The TVS screen is where the clamp voltage of the TVS device under test or SPD surge protector is displayed The measurement is performed by pressing the TEST button on the f...

Страница 22: ...ations settings and show the message Shutting Down please wait In the event of an abnormal lock up of the instrument or its firmware the unit can be forced into a hardware power down by depressing the...

Страница 23: ...een warning clicking the Acknowledge button to signify that the warn ing has been read and the potential hazard is understood Step 4 Enter the default passcode 1_2_3_4 to unlock the instrument The ins...

Страница 24: ...AC the battery is being maintained in a charged state The charger automatically regulates as the battery condition determines between a fast charge stated gradient green battery icon and a trickle cha...

Страница 25: ...measurement is performed by driving a fixed constant current through the device and recording what voltage appears across the device often referred to as the clamping voltage The clamping voltage is d...

Страница 26: ...de LOG mode refer to Log screen section A check in the footer panel indicates this mode has been activated Step 4 Press the TEST button on the front panel of the instrument The red high voltage LED wi...

Страница 27: ...efault option Step 3 If required enable the GDT Prefire mode which will force the GDT to be fired three times pre ionization before the measurement is recorded The GDT Prefire option is disabled when...

Страница 28: ...PD If the SPD is a combination type comprising MOV GDT it is recommended to manu ally set the instrument to its MOV mode by pressing the MOV button In this mode the instrument will raise the voltage a...

Страница 29: ...be used to download the new firmware file V TEST IIxxx hex to the instrument This is a third party software developed by MikroElektronika for this purpose refer to Figure 3 Figure 3 Bootloader PC app...

Страница 30: ...n to connect 6 Connect instrument to the PC using a standard USB printer cable 7 Start the USB HID Bootloader PC application and click the Connect button green LED solid PC application is now connecte...

Страница 31: ...placing main battery It is recommended that AA NiMH cells with at least 2300 mAh be used in this instrument refer to General specifications section Typically such batteries can withstand 500 recharge...

Страница 32: ...tery cover 5 Remove an AA cell of the main battery 6 Remove the six screws securing the back half of instrument enclosure to the front half Carefully sepa rate the two halves avoiding placing any stra...

Страница 33: ...ze quantity Type AA 5 ea Battery type NiMH supplied Battery life typical 200 hours idling Operating temperature 10 C 50 C Storage temperature 10 C 60 C indefinitely to 40 C for 100 hrs Relative humidi...

Страница 34: ...34 2661740000 03 02 2021 Physical dimensions Physical dimensions 204 5 mm 81 mm 222 mm...

Страница 35: ...LCF S 2726740000 550 950 VPU AC I 3 R 275 25 LCF S 2726750000 550 950 VPU AC I 4 275 25 LCF S 2726780000 550 950 VPU AC I 4 R 275 25 LCF S 2726790000 550 950 VPU AC I 1 N PE 305 100 S 2726800000 n a 5...

Страница 36: ...R 300 12 5 2591490000 423 517 500 900 VPU AC I 300V 12 5kA LCF 2 VPU AC I 0 300 12 5 LCF 2636900000 800 1363 VPU AC I 3 1 300 12 5 LCF 2636910000 800 1363 500 900 VPU AC I 3 1 R 300 12 5 LCF 263692000...

Страница 37: ...150 50 2591680000 297 363 VPU AC II 3 150 50 2591690000 297 363 VPU AC II 3 R 150 50 2591700000 297 363 VPU AC II 4 150 50 2591710000 297 363 VPU AC II 4 R 150 50 2591000000 297 363 VPU AC II 300V 50...

Страница 38: ...VPU AC II 3 350 50 2591100000 558 682 VPU AC II 3 R 350 50 2591110000 558 682 VPU AC II 4 350 50 2591120000 558 682 VPU AC II 4 R 350 50 2591130000 558 682 VPU AC II 2 350 50 2637010000 558 682 VPU A...

Страница 39: ...U AC II US 1 120 50 2730450000 297 363 VPU AC II US 1 R 120 50 2730460000 297 363 VPU AC II US 2 120 50 2730470000 297 363 VPU AC II US 2 R 120 50 2730480000 297 363 VPU AC II US 4 120 50 2730490000 2...

Страница 40: ...736490000 423 517 VPU AC II US 0 240 50 Y 2736500000 423 517 VPU AC II US 0 N PE 240 Y 2736520000 n a 500 900 VPU AC II US 277V 50kA VPU AC II US 0 277 50 2730560000 558 682 VPU AC II US 1 277 50 2730...

Страница 41: ...1215 1485 VPU AC II US 3 R 600 35 2730780000 1215 1485 VPU AC II US 4 R 600 35 2730770000 1215 1485 VPU PV I II VPU PV I II 3 1000 2530610000 675 825 VPU PV I II 3 R 1000 2530620000 675 825 VPU PV I I...

Страница 42: ......

Страница 43: ......

Страница 44: ...www weidmueller com Weidm ller Interface GmbH Co KG Klingenbergstra e 26 32758 Detmold Germany T 49 5231 14 0 F 49 5231 14 292083 www weidmueller com Order number 2661740000 03 02 2021...

Отзывы: