General
The wavePak is a DIN rail mounted, signal Isolator/Converter for
Industrial Current/Voltage signals. It can be used with 4-20 mA loop
powered input devices using the Field Power Supply provided.
Current Test Points
To monitor current signals, connect a multimeter (set to a suitable
milliamp range) across pins 2 (+) and 4 (−) for the inputs
or 8 (−) and 6 (+) for outputs.
Cleaning
The case can be wiped with a damp cloth. De-energise the unit before
cleaning.
Input
PS
Out
V +
I +
pwr +
pwr -
I +
Com
V +
Com