- 8 -
ATEX Information
Certificate number DEMKO 11 ATEX 150194X
Ambient range:
-40°C
≤
Tamb
≤
+75°C for models with suffix of “-T”;
0°C
≤
Tamb
≤
+60°C for models without suffix of “-T”
Certification string: Ex nA nC IIC T4 Gc
Rated Cable Temperature:
≧
100°C
Standards covered:
EN 60079-0:2012+A11:2013, EN 60079-15:2010
The conditions of safe usage:
These devices are to be installed in an ATEX certified IP54
enclosure accessible only with use of a tool and used in an area of
not more than pollution degree 2 as defined by EN 60664-1.
Use a conductor wire of size 0.2 mm² or greater
Conductors suitable for use in an ambient temperature of 93°C
must be used for the Power Supply Terminal.
PROVISIONS SHALL BE MADE, EITHER IN EXTERNAL TO
THE APPARATUS, TO PREVENT THE RATED VOLTAGE
BEING EXCEEDED BY THE TRANSIENTS DISTURBANCES OF
MORE THAN 40 %
.
NOTE
Suitable for use in Class I, Division 2, Groups A, B, C and D
hazardous locations, or nonhazardous locations only.
WARNING
EXPLOSION HAZARD - Do not disconnect equipment while the
circuit is live or unless the area is known to be free of ignitable
concentrations.
WARNING
EXPLOSION HAZARD - Substitution of any component may
impair suitability for Class 1, Division 2
WARNING
EXPLOSION HAZARD – Servicing, replacing, and installing the
product can only take place is an area that is non-hazardous.