Mounting
PSRW | 3-3
3
3.5 INSTRUCTION TO CABLE AND TERMINALS
Terminal tightening torque: 5 ÷ 7 lb-in (0.6 ÷ 0.7 Nm).
Wire size range: AWG 12 ÷ 30, (solid/stranded).
Use 60/75 °C (140/167 °F) copper (Cu) conductor only.
We recommend the use of separate power supplies for the PSRW to other electrical power equipment (electric
motors, inverters, frequency converters) or other sources of disturbance.
Cables used for connections of longer than 50 m must have a cross-section of at least 1 mm
2
(AWG16).
ATTENTION!
Install the PSRW in an enclosure with a protection class of at least IP54.
ATTENTION!
Turn off the PSRW before connect the inputs/outputs.
ATTENTION!
The supply voltage to the units must be 24 Vdc ± 20 % (PELV, in compliance with the standard EN
60204-1 (
Chapter 6 TECHNICAL SPECIFICATION on page 6-1
ATTENTION!
Do not use the PSRW like supply to external devices.
ATTENTION!
The same voltage reference (0 Vdc) must be used for all system components.
3.6 USB INPUT
The PSRW includes a USB 2.0 connector for connection to a personal computer and access the configurator tool
WPS manual available for download on the website:
.
Содержание PSRW
Страница 2: ......
Страница 3: ...User s Manual Series PSRW Language English Document 10005909449 01 Publication Date 05 2019...
Страница 10: ...Introduction 1 4 PSRW 1...
Страница 12: ...Description 2 2 PSRW 2...
Страница 18: ...Operation Diagram 4 2 PSRW 4...
Страница 24: ...Signals 5 6 PSRW 5...
Страница 28: ...Diagnosis 7 2 PSRW 7...
Страница 34: ...Connection Examples 8 6 PSRW 8...
Страница 56: ...Product Use With Safety 10 2 PSRW 10...
Страница 58: ...11 Modifications 11 2 PSRW...
Страница 59: ...Declaration Of Conformity PSRW 12 1 12 12 DECLARATION OF CONFORMITY...