5
DETAILED PARAMETER DESCRIPTION
P0236 - Analog input AI1 offset (unipolar MVC4 board)
Adjustable range:
-100.0 to 100.0 %
Factory setting:
0.0 %
Acesso:
Menu
→
Configurations
→
I/O
→
Analog inputs
Description:
Refer to P0234.
P0237 - AI2 signal function
Adjustable range:
0 to 3
Factory setting:
0
Acesso:
Menu
→
Configurations
→
I/O
→
Analog inputs
Description:
When the option 0 (P0221/P0222) is selected, AI2 is able to provide the reference (provided that programmed
so in P0221/P0222), subject to the reference limits (P0133, P0134) and ramp action (P0100 to P0103).
Option 3 (Process Variable) defines the AI2 input as the PID regulator feedback signal (e.g., pressure or tem-
perature sensor, etc.), provided that P0524 = 0.
Table 5.38:
AI2 signal function
Function
0
1
Not Used
2
Maximum torque current
3
PID process variable
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0238 - Analog input AI2 gain (bipolar MVC4 board)
Adjustable range:
0.000 to 9.999
Factory setting:
1.000
Acesso:
Menu
→
Configurations
→
I/O
→
Analog inputs
Description:
AI2’ = -2 V, meaning that the motor will run in reverse direction with a speed reference absolute value equal to
2 V.
The internal value of AI2’ is the result of the following equation:
AI2’
= (
AI2
+
OFFSET
100
×
10 V
)
×
Gain
Example:
AI2 = 5 V, OFFSET = -70 % and Gain = 1.00
AI2’
= (
5
+
(
-70
)
100
×
10 V
)
×
1 = -2 V
AI2’ = -2 V, meaning that the motor will run in reverse direction with a speed reference absolute value equal to
2 V.
MVW3000 | 5-46
Содержание MVW3000 Series
Страница 2: ......
Страница 58: ...1 QUICK REFERENCE OF PARAMETERS AND FAULTS MVW3000 1 52...
Страница 62: ...2 SAFETY INSTRUCTIONS MVW3000 2 4...
Страница 192: ...6 SPECIAL FUNCTIONS MVW3000 6 4...
Страница 262: ...7 DIAGNOSTICS AND TROUBLESHOOTING MVW3000 7 70...
Страница 263: ......