General Information
CFW501 | 2-1
2
2 GENERAL INFORMATION
2.1 ABOUT THE MANUAL
This manual presents information necessary for the configuration of all the functions and parameters of the frequency
inverter CFW501. This manual must be used together with the user’s manual of the CFW501.
The text provides additional information so as to make the use and programming of the CFW501 easier in certain
applications.
The standard value for the parameters related to speed described in this manual assumes a standard 4-pole
motor, that is, with synchronous speed of 1500 rpm (50 Hz) or 1800 rpm (60 Hz).
Table 2.1: Setting of the speed
shows the setting suggested of those parameters for other number of poles. Furthermore,
parameter P0402 must be set with the data on the motor nameplate; if not available, use the rated speed.
Table 2.1:
Setting of the speed parameters
Number of
Poles
P0133
P0134 and P0145
P0146
P0147
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
2
180 rpm
3000 rpm
3600 rpm
2000 rpm
2400 rpm
1000 rpm
1200 rpm
4
90 rpm
1500 rpm
1800 rpm
1000 rpm
1200 rpm
50 0rpm
600 rpm
6
60 rpm
1000 rpm
1200 rpm
667 rpm
800 rpm
333 rpm
400 rpm
8
45 rpm
750 rpm
900 rpm
500 rpm
600 rpm
250 rpm
300 rpm
NOTE!
“The specific HVAC functions present on the CFW501 can only be activated with the connection of
the HVAC plug-in module (CFW500-CRS485). Other plug-in modules can be used, but in this case
the HVAC application must be turned off by means of parameter P1001.”
2.2 TERMINOLOGY AND DEFINITIONS
2.2.1 Terms and Definitions Used
I
nom
:
inverter rated current by P0295.
Overload Duty:
in the CFW501 there is no difference in the operating duty between “Light - Normal Duty” (ND)
and “Heavy - Heavy Duty” (HD). Thus, the overload duty adopted for the CFW501 is equivalent to the HD standard,
that is, the maximum overload current is 1.5 x I
nom
for one minute of continuous operation.
Rectifier:
input circuit of the inverters that transforms the input AC voltage into DC. It is formed by high-power
diodes.
IGBT:
insulated Gate Bipolar Transistor - basic component part of the output inverter bridge. It works as an
electronic switch in the saturated (closed switch) and cut-off (open switch) modes.
DC Link:
intermediary circuit of the inverter; voltage in direct current obtained by rectifying the power supply
alternate voltage or external supply; it supplies the output inverter bridge with IGBTs.
Pre-Charge Circuit:
charges the capacitors of the DC link with limited current, avoiding current peaks in the
inverter power-up.
Braking IGBT:
it works as a switch to turn on the braking resistor. It is controlled by the DC link level.
Содержание CFW501 V1.8X
Страница 2: ......
Страница 8: ...Summary...
Страница 34: ...General Information 2 4 CFW501 2...
Страница 38: ...About the CFW501 3 4 CFW501 3...
Страница 42: ...HMI and Basic Programming 4 4 CFW501 4...
Страница 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Страница 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Страница 76: ...Available Motor Control Types 8 4 CFW501 8...
Страница 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Страница 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Страница 148: ...Faults and Alarms 14 12 CFW501 14...