Functions Common to All the Control Modes
11-6 | CFW300
11
11.2.4 Current Limitation Type "Decelerate Ramp" P150 = 0 or 1
It prevents the motor from collapsing during torque overload in the acceleration or constant frequency.
Actuation: if the motor current exceeds the value set in P135, a null value is forced for the frequency ramp input
forcing the motor deceleration. When the motor current reaches a value below P135 the motor accelerates
again. Look at
P135 - Maximum Output Current
Adjustable
Range:
0.0 to 40.0 A
Factory
Setting:
1.5 x I
nom
Properties:
Description:
Current level to activate the current limitation for the Ramp Hold and Decelerate Ramp modes, as per
(a) and (b), respectively. In order to disable the current limitation, you must set parameter
P135 > 1.9 x I
nom
.
Time
Time
Time
Time
Time
During
Acceleration
Ramp
acceleration
(P100)
Ramp
deceleration
(P101)
It decelerates
by emergency
ramp
Deceleration
(b) "Ramp Deceleration"
(a) "Ramp Hold"
Output
frequency
Output
frequency
Motor current
Motor current
Motor current
P135
P135
P135
Output
frequency
Figure 11.5:
(a) and (b) Actuation modes of current limitation via P135
Содержание CFW300 V1.3X
Страница 2: ......
Страница 8: ...Contents...
Страница 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Страница 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Страница 72: ...V f Scalar Control 9 10 CFW300 9...
Страница 80: ...VVW Vector Control 10 8 CFW300 10...
Страница 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Страница 132: ...Reading Parameters 15 6 CFW300 15...