Reading Parameters
15-4 | CFW300
15
P029 - Power Hardware Configuration
Refer to
Section 6.1 INVERTER DATA on page 6-1
P030 - Power Module Temperature
Adjustable
Range:
0.0 to 200.0 ºC (32 °F to 392 °F)
Factory
Setting:
Properties:
ro
Description:
Temperature in ºC measured inside the power module by the internal NTC.
P037 - Motor Overload Ixt
Refer to
Section 14.1 MOTOR OVERLOAD PROTECTION (F072 AND A046) on page 14-1
.
P038 - Encoder Speed
Adjustable
Range:
-9999 to 9999 rpm
Factory
Setting:
Properties:
ro
Description:
This parameter presents the instant speed of the encoder in revolutions per minute (RPM); the measurement is
not filtered and it is updated every 6 ms.
P039 - Encoder Pulse Counter
Adjustable
Range:
0 to 9999
Factory
Setting:
Properties:
ro
Description:
Using this parameter it is possible to check the number of pulses counted from the encoder in quadrature.
The count can be incremented from 0 to 9999 (clockwise) or decremented from 9999 to 0 (counterclockwise).
P045 - Enabled Fan Time
Adjustable
Range:
0 to FFFF(hexa)
Factory
Setting:
Properties:
ro
Description:
It indicates the total number of hours that the heatsink fan remained connected. This value is kept even when
the inverter is disconnected. Setting P204 = 2, the value of parameter P045 goes to zero.
Содержание CFW300 V1.3X
Страница 2: ......
Страница 8: ...Contents...
Страница 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Страница 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Страница 72: ...V f Scalar Control 9 10 CFW300 9...
Страница 80: ...VVW Vector Control 10 8 CFW300 10...
Страница 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Страница 132: ...Reading Parameters 15 6 CFW300 15...