I/O Expansion Modules
E
ng
lis
h
6 | CFW100
1. With the inverter powered down, remove its front
cover (
2. Fit the accessory to be installed as shown in
.
3. Power up the inverter.
5 CONFIGURATIONS
The CFW100-IOA connections must be done to the I/O
expansion connector according to
The pins of the accessory connector are presented in
Table 1:
Signals of the I/O expansion connector
Connector Description
Specifications
6
GND
Reference 0 V Not interconnected with PE.
7
AI1
Analog
Input 1
Isolated voltage input,
levels: (0 to 10) V or (0 to
20) mA or (4 to 20) mA.
Resolution: 10 bits.
Impedance: 100 kΩ for
voltage input and 500 Ω
for current input.
Programmable functions.
Maximum accepted
voltage: 30 Vdc.
8
+ 10 V
Reference
+ 10 V for
potentiometer
Power supply: + 10 Vdc.
M a x i m u m c a p a c i t y:
50 mA.
Tolerance: ±5 %.
9
AO1
Analog
Output 1
Insulated output, levels:
(0 to 10) V or (0 to 20) mA
or (4 to 20) mA.
Resolution: 10 bits.
Programmable functions.
R
L
≥ 10 kΩ (0 to 10 V) or
R
L
≤ 500 Ω (0 to 20 mA
/ 4 to 20 mA).
10
GND
Reference 0 V Not interconnected with PE.
Counter-
clockwise
≥
5 k
Clockwise
The location of switch S1.1 to select the type of signal
at the analog input can be better viewed in
. To use the analog input with voltage
signal, you must set switch S1.1 = OFF and related
parameters, for current input you set S1.1 = ON, as per