15-15
15
Faults and Alarms
Description:
This parameter allows disabling the actuation of F185 fault – Fault in the preload contactor.
If P0355 = 0, the Fault in the preload contactor will remain deactivated. F185 fault will not be generated.
When the inverter is a frame size E with DC power supply it’s necessary to adjust P0355 = 0.
P0356 – Dead Time Compensation
Adjustable
Range:
0 = Off
1 = On
Factory
Setting:
1
Properties:
CFG
Access groups
via HMI:
01 PARAMETER GROUPS
45 Protections
Description:
This parameter must be kept always in 1 (On). Only in special maintenance cases the value 0 (Off) can be used.
P0357 – Line Phase Loss Time
Adjustable
Range:
0 to 60 s
Factory
Setting:
3 s
Properties:
Access groups
via HMI:
01 PARAMETER GROUPS
45 Protections
Description:
It configures the time for the line phase loss indication (F006).
If P0357 = 0, the function remains disabled.
NOTE!
The function Phase Loss will be automatically disabled when detected some of the models:
CFW11
0010 S 2024, CFW11 0006 S 2024FA
or
CFW11 0007 S 2024 FA
.
If the inverter has single-phase power supply, it is necessary to adjust P0357 = 0 to disable the fault
F006.
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...