Faults and Alarms
15-2
15
NOTE!
In order to assure the conformity of the CFW-11 motor overload protection with the UL508C
standard, observe the following:
The "TRIP" current is equal to 1.25 times the motor nominal current (P0401) adjust in the
"Oriented Start-up" menu.
The maximum allowed value for P0398 (Motor Service Factor) is 1.15.
Parameters P0156, P0157 and P0158 (Overload Current at 100 %, 50 % and 5 % of the
rated speed, respectively) are automatically adjusted when the parameter P0401 (Motor Rated
Current) and/or P0406 (Motor Ventilation) are adjusted in the "Oriented Start-up" menu. If the
parameters P0156, P0157 and P0158 are manually adjusted, the maximum allowed value
for those parameters is 1.05 x P0401.
15.2 MOTOR OVERTEMPERATURE PROTECTION
ATTENTION!
The PTC must have a reinforced insulation against the live parts of the motor and of the installation.
This protection performs the motor overtemperature protection by means of the alarm (A110) and the fault
(F078) indication.
The motor must have a PTC type temperature sensor.
An analog output supplies constant current for the PTC (2 mA), while an inverter analog input reads the voltage
across the PTC and compares it with the limit values for fault and alarm. Refer to the
.
When those values are exceeded, the alarm or fault indication occurs.
The analog outputs AO1 and AO2 of the control module, as well as the analog outputs existent on the accessory
modules AO1-B and AO2-B (IOB) can be used to supply the constant current for the PTC. Therefore it is necessary
to configure the DIP switches of the output for current and to set the output function parameter for 13 = PTC.
The analog inputs AI1 and AI2 of the control module, as well as the analog inputs existent on the accessory
modules AI3 (IOB) and AI4 (IOA) can be used to read the PTC voltage. Therefore it is necessary to configure
the input DIP switch for voltage and to set the input function parameter for 4 = PTC. Refer to the parameter
P0351 on the
Section 15.3 PROTECTIONS [45] on page 15-4
NOTA!
In order that this function works properly, it is important to keep gains and offset of the analog input
and output in the default values.
Table 15.1 -
A110 and F078 trip levels
Action
PTC
AI voltage
A110 occurs during the temperature increase
R
PTC
>3.51 k
Ω
V
AI
>7.0 V
F078 trips during the temperature increase
R
PTC
>3.9 k
Ω
V
AI
>7.8 V
Resets A110 alarm
150
Ω
< R
PTC
<1.6 k
Ω
0.3<V
AI
<3.2 V
Allows the reset of the F078 fault
150
Ω
< R
PTC
<1.6 k
Ω
0.3<V
AI
<3.2 V
F078 trips (minimum resistance detection)
R
PTC
<60
Ω
<0.12 V
Содержание CFW-11 Series
Страница 2: ......
Страница 54: ...2 4 2 General Information ...
Страница 58: ...About the CFW 11 3 3 4 ...
Страница 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Страница 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Страница 94: ...Available Control Types 8 2 8 ...
Страница 118: ...VVW Control 10 8 10 ...
Страница 182: ...Functions Common to All the Control Modes 12 26 12 ...
Страница 220: ...Dynamic Braking 14 4 14 ...