20 l Automatic Voltage Regulator – AVR-A-OPT-04E / AVR-A-OPT-05PE
14 PROBLEMS, CAUSES AND CORRECTIVE ACTIONS
Table 14.1
Problems
Causes
Corrective Actions
There is circulation of reactive power
between alternators when operating in
parallel.
Phases sequence (R-S-T) incorrectly
connected;
CT connections are inverted;
Droop adjustment excessively low.
Connect phase sequence correctly.
Correctly polarize the CT in the phase shown
below:
Increase droop adjustment, rotating trimpot
P2 clockwise (CW).
Generated voltage decreases when load is
applied, and it doesn’t return.
Dropping speed of the driving machine;
Under frequency protection engaged.
Correct speed regulation.
Adjust Under frequency protection by rotating
trimpot P5 clockwise (CW).
Alternator voltage does not increase.
Residual voltage excessively low
Terminals F (+) and F (-) are inverted.
With the regulator switched- on, use external
battery (12Vcc) to force excitation (*).
Invert F (+) and F (-).
Generated voltage oscillates at no load.
Dynamic not well adjusted.
Alternator excitation voltage excessively
low.
Adjust trimpots P3 and P4;
Insert 10
Ω
/100W resistor in series with field.
Voltage oscillates at a specific load point.
Third harmonic of the auxiliary coil is
high.
Eliminate auxiliary coil and proceed with the
connections according to the diagrams of
page 13.
Voltage surges.
Lack of sensing.
Faulty electronic circuit.
Sensing voltage incompatible with
regulator.
Check if alternator phases are present in the
sensing.
If the regulator is encapsulated, replace it.
(*)For battery diesel generator where the alternator neutral is grounded battery should always be used independently.
15 PREVENTIVE MAINTENANCE
Periodical inspections of
the equipment are required to ensure they are clean, dust and moisture free. It is essential that
all terminal and connections are kept free from corrosion.
16 WARRANTY
See Installation and Maintenance Manual for WEG Alternators.
WEG Group - Energy Business Unit
Jaraguá do Sul - SC - Brazil
Telefono: 55 (47) 3276-4000
www.weg.net
P1
P2
S1
S2
Alternator
Load
Содержание AVR-A-OPT-04E
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 19: ...www weg net Automatic Voltage Regulator AVR A OPT 04E AVR A OPT 05PE l 19 Figure 13 1 Test diagram ...
Страница 22: ......
Страница 24: ......
Страница 33: ...www weg net Regulador Automático de Tensión AVR A OPT 04E AVR A OPT 05PE l 33 Figura 13 1 Diagrama de prueba ...
Страница 36: ...www weg net Regulador Automático de Tensão AVR A OPT04E AVR A OPT 05PE 36 INDEX ...
Страница 38: ...www weg net Regulador Automático de Tensão AVR A OPT04E AVR A OPT 05PE 38 ...
Страница 47: ...www weg net Regulador Automático de Tensão AVR A OPT 04E AVR A OPT 05PE l 47 Figura 13 1 Diagrama para teste ...
Страница 49: ...www weg net Regulador Automático de Tensão AVR A OPT 04E AVR A OPT 05PE l 49 NOTAS ...
Страница 50: ...www weg net Regulador Automático de Tensão AVR A OPT04E AVR A OPT 05PE 50 ...