www.weg.net
ABW - Air Circuit Breaker | 37
4.4.2 Type A units
Long delay
Current of
adjustment
Iu = In x ...
0.5
0.6
0.7
0.8
0.9
1.0
Ir = Iu x ...
0.80
0.83
0.85
0.88
0.9
0.93
0.95
0.98
1.0
Time of
adjustment
(s)
tr @ 1.5xIr
12.5
25
50
100
200
300
400
500
Off
tr @ 6xIr
0.5
1
2
4
8
12
16
20
Off
tr @ 7.2xIr
0.34
0.69
1.38
2.7
5.5
8.3
11
13.8
Off
Precision: ± 15% ou < 100ms
Short delay
Current of
adjustment
Isd = Ir x ...
1.5
2
3
4
5
6
8
10
Off
Precision: ± 10%
Time of adjustment
(s) @ 10xIr)
tsd (I²t Off) @ 10xIr
0.05
0.1
0.2
0.3
0.4
tsd (I²t On) @ 10xIr
0.1
0.2
0.3
0.4
I²t Off
Opening min. time (ms)
20
80
160
260
360
Opening max. time (ms)
80
140
240
340
440
Adjustment of current
Current of
adjustment
Ii = In x ...
2
3
4
6
8
10
12
15
Off
Opening time: < 50ms
Shortage current to ground
Current of
adjustment
Ig = In x ...
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1
Off
Precision: ± 10% (Ig>0.4In); ±20% (Ig≤0.4In)
Time of adjustment
(s) @ 1xIn
tg (I²t Off) @ 1xIn
0.05
0.1
0.2
0.3
0.4
tg (I²t On) @ 1xIn
0.1
0.2
0.3
0.4
I²t Off
Opening min. time (ms)
20
80
160
260
360
Opening max. time (ms)
80
140
240
340
440
Adjustment of time (s) @ 1xIn
Current of
adjustment (A)
Ig
0.5
1
2
3
5
10
20
30
Off
Time of
adjustment (s)
Alarm (ms)
140
230
350
800
950
Trip (ms)
140
230
350
800
Precision: ± 15%
Содержание ABW Series
Страница 2: ......
Страница 3: ...User Manual Series ABW Air Circuit Breaker Language English...
Страница 4: ......
Страница 7: ......
Страница 56: ......
Страница 57: ...Manual del Usuario S rie ABW Interruptor Abierto Idioma Espa ol...
Страница 58: ......
Страница 61: ......
Страница 110: ......
Страница 111: ...Manual do Usu rio S rie ABW Disjuntor Aberto Idioma Portugu s...
Страница 112: ......
Страница 115: ......
Страница 157: ...ABW Disjuntor Aberto 157 www weg net 6 2 PROTE O DE CURTO RETARDO S Figura 6 2 Prote o de curto retardo S...
Страница 160: ...160 ABW Disjuntor Aberto www weg net 6 5 PR ALARME Figura 6 5 Pr alarme...