LX3V-4DA module
8
WECON Technology Co., Ltd.
6.
Caution regarding operation
1)
Check whether the output wiring and/or expansion cables are properly connected on LX3V-4DA
analog special function block.
2)
Check that the LX3V system configuration rules have not been broken, i.e. the number of blocks
does not exceed 8 and the total system I/O is equal or less than 256 I/O.Ž
3)
Ensure that the correct output mode has been selected for the application.
4)
Check that there is no power overload on either the 5V or 24V power source, remember the
loading on the LX3V MPU or a powered extension unit varies according to the number of
extension blocks or special function blocks connected.•
5)
Put the main processing unit into RUN.
6)
After turning on or off the 24 VDC power for analog signals, the analog output may fluctuate for
approximately 1 second. This is due to time delays in the power supply from the MPU or
differences in start time. For this reason, be sure to take preventive measures so that this output
fluctuation will not affect the external units.
7.
Adjustment of I/O characteristics
1)
I/O characteristics
The standard characteristics (factory default) are shown by the solid lines in the figure below. These
characteristics can be adjusted according to the conditions of the user’s system.