LX3V-2PT2DAI-BD
4
WECON Technology Co., Ltd.
5.
Wire Connection
Description:
1)
2-wire PT100: When using the first channel, L1- and VI- should be shorted with wires, and the
two leads of the sensor should be connected with L1 + and L1- respectively. Similarly, use the
second channel.
2)
3-wire PT100: When using the first channel, two of the same color leads are respectively
connected to L1- and VI-, and the other different color is connected to L1 +. Similarly, use the
second channel.
Warning:
Make sure cut off the electricity before installation/disassembly, to prevent electric shock or
product damages.
Caution:
1)
Please keep the signal cable from the high-voltage cable at lease 100mm.
2)
The shielding wire cable shall be grounded. But their grounding point can be the same with
high-voltage lines.
3)
Never connect cable with forbidden size.
4)
Fix the cable, so that the stress does not act on the terminal board or the cable connection
area.
5)
The screwing torque of the terminal is from 0.5 to 0.6N.m. Fasten tight to prevent malfunction.
6)
Keep the redundant terminals empty.
5.1 Applicable Cables
Use AWG25-16 to connect the output equipment
The maximal screwing torque is from 0.5 to 0.6N.m
The use of different types of cables might cause poor contact between the terminals. It is better to
use pressed terminals.
Table 5-1
Line
type
Cross sectional
area(mm
2
)
End-of-pipe treatment
AWG26
0.1288
Stranded cable: stripped jacket, rub
Conductor, then connect the cable.
......
......