Gas sUPPlY

tYPiCaL 20 LP ProPanE gaS SUPPLY inStaLLation

The remote tank enclosure kit provided with your Weber Built-In grill shall be used for 
installations using a 20 lb LP cylinder, mounted in an “island” structure.
The remote tank enclosure shall house the included hose and regulator assembly and 
gas connections, the tank bracket and the fuel scale for connecting a remote mounted 
LP cylinder to the Summit

®

 Built-In gas grill. The hose and regulator is listed as a 

required part of the CSA listed Summit

®

 Built-In gas grill.

A properly installed tank enclosure meets the requirements for venting, tank retention 
and separation of the LP cylinder from a heat source as outlined in the ANSI Standard 
for Outdoor Cooking Gas Appliances, Z21.58/CSA 1.6 for LP enclosures.
You need to hire a licensed contractor or licensed plumber and they need to follow the 
requirements described in the ANSI Standard for Outdoor Cooking Gas Appliances, 
Z21.58/CSA 1.6 for LP enclosures.
The requirements described in the Standard for Outdoor Cooking Gas Appliances, 
Z21.58/CSA 1.6. are as follows;

A remote enclosure for an LP gas cylinder shall be ventilated by openings at both 
the upper and lower levels of the cylinder. This shall be accomplished by one of the 
following:

A)  One side of the remote LP cylinder enclosure shall be completely open; or 

B)  If the remote LP cylinder enclosure is designed to have four sides, a top and a 

bottom, ventilation is required for the remote LP cylinder enclosure;

1)  There should be at least two ventilation openings, (a hole or group of 

holes, for the purpose of ventilation) in the sidewalls of the island structure. 
The openings should be located within 5 inches (127mm) of the top of the 
enclosure. The ventilation openings should be equally sized and spaced at 
a minimum of 90 degrees, and be unobstructed. The openings shall have 
a total free open area of not less than 20 square inches. (This relates to 1 
square inch of ventilation area, per pound of stored fuel capacity).

2)  Ventilation openings (a hole or group of holes, for the purpose of ventilation) 

should be provided at floor level. The ventilation openings should have a total 
free area of not less than 10 square inches. (This relates to 1/2 square inch 
of ventilation area, per pound of stored fuel capacity). There should be at 
least two ventilation openings if the ventilation openings at floor level are in 
the sidewall. The ventilation openings should be within 5 inches (127mm) of 
the floor. The ventilation openings should be of equal size and be spaced at 
a minimum of 90 degrees, and should be unobstructed. 

3)  The minimum size of the ventilation hole (s) should not be less than 1/4 inch. 
4)  The ventilation openings in the sidewalls should not allow venting into 

the empty or “hollow” area of the “island”. If a gas leak should occur or 
the LP cylinder should vent in the LP cylinder enclosure, the gas should 
not be allowed to vent or migrate into the empty or “hollow” area of the 
“island”.  Ventilation openings in the sidewalls of the enclosure should only 
communicate with the outside of the “island” structure, so that the gas can 
dissipate outside of the “island” structure. 

C) If the remote LP cylinder enclosure has four sides, a top and a bottom, and is 

intended for installation in a built-in “island” enclosure;

1)  At least one ventilation opening (a hole or group of holes, for the purpose 

of ventilation) needs to be on one side of the enclosure that communicates 
with the outside of the “island” structure. If a gas leak should occur or the 
LP cylinder should vent in the LP cylinder enclosure, the gas should not 
be allowed to vent or migrate into the empty or “hollow” area of the “island”.  
Ventilation openings should only communicate with the outside of the “island” 
structure, so that the gas can dissipate outside of the “island” structure. The 
ventilation opening should be located within 5 inches (127mm) of the top of 
the enclosure, and should have a total free area of 20 square inches. (This 
relates to 1 square inch of ventilation area, per pound of stored fuel).

2)  At least one ventilation opening (a hole or group of holes, for the purpose 

of ventilation) needs to be on one side of the enclosure that communicates 
with the outside of the “island” structure, at the bottom. If a gas leak should 
occur or the LP cylinder should vent in the LP cylinder enclosure, the gas 
should not be allowed to vent or migrate into the empty or “hollow” area of 
the “island”.  Ventilation openings should only communicate with the outside 
of the “island” structure, so that the gas can dissipate outside of the “island” 
structure. The ventilation opening should be located within 5 inches (127mm) 
of the bottom of the enclosure, and should have a total free area of 10 square 
inches. (This relates to 1/4 square inch of ventilation area, per pound of 
stored fuel).

3) The minimum size of the ventilation hole (s) should not be less than 1/4 inch 

(6.35mm).

dangEr

Use of any hose and regulator assembly other than that 
provided or recommended by weber-Stephen Products inc. 
could be dangerous, and may not provide adequate gas 
supply to the Summit

®

 built-in gas grill, and could result in 

a fire or an explosion causing serious bodily injury or death, 
and damage to property. 

dangEr

failure to build a remote LP cylinder enclosure for a single 
20 lb cylinder only, following the requirements for ventilation, 
cylinder retention and separation of the LP cylinder from a 
heat source, listed in the anSi Standard for outdoor Cooking 
gas appliances, anSi Z21.58 CSa 1.6, could be dangerous, 
and could result in a fire or an explosion causing serious 
bodily injury or death and damage to property.

If you do not follow the DANGER statements exactly, the Warranty on the Summit

®

 Built-

In gas grill will be voided. 

D) The remote LP cylinder enclosure should be constructed with non-combustible 

materials. The remote LP cylinder enclosure should isolate the LP cylinder from the 
burner compartment, so that it provides shielding from radiation, be a flame barrier 
and provide protection from foreign material such as hot drippings. 

E) There should be a minimum of 2 inches (50.8mm) between the ground and the floor of 

the remote LP cylinder enclosure. 

F) The LP cylinder valve should be readily accessible for hand operation. A door on the 

remote LP cylinder enclosure to gain access to the LP cylinder valve is acceptable, 
provided it is non-locking and can be opened without the use of tools. 

www.wEBEr.COM

®

Содержание Summit 43267

Страница 1: ...WARNING 1 Do not store or use gasoline or other flammable liquids or vapors in the vicinity of this or any other appliance 2 An LP cylinder not connected for use shall not be stored in the vicinity o...

Страница 2: ...cts or other reproductive harm Wash hands after handling this product LIQUID PROPANE GAS UNITS ONLY m Use the regulator that is supplied with your Weber Tank Enclosure Kit m Do not attempt to disconne...

Страница 3: ...ose from grill manifold to gas supply bulkhead must not exceed 58 147cm The 3 8 9 52mm Side Burner accessory hose not included must not exceed 58 147cm NOTE IF YOU HAVE PURCHASED A SIDEBURNER If you h...

Страница 4: ...0 Dimensions 1 24 minimum 610 mm 24 minimum 610 mm 2 4 3 4 120 65 mm 4 3 4 120 65 mm 3 6 1 4 158 75 mm 6 1 4 158 75 mm 4 10 1 2 266 7 mm minimum 10 1 2 266 7 mm minimum 5 23 584 2 mm 23 584 2 mm 6 34...

Страница 5: ...id 1 Cookbox 1 Lid 1 Cookbox 1 Front Frame Rail 1 Rear Frame Rail 1 Rear Panel Assembly 1 Bottom Shelf 1 Left Door 1 Right Door 1 Warming Rack 1 Right Enclosure Panel 1 Left Enclosure Panel 1 Front Ve...

Страница 6: ...k 4 Rotisserie Motor 1 Rotisserie Bracket 1 Smoker 1 Smoker Bar 1 1 2 inch Bolts 20 x 1 2 inch Bolt 10 Nylon Washer 10 Hair Pin Cotter 2 10 32 x 1 4 inch Steel Screw 5 10 Sheet Metal Screw 3 Plastic A...

Страница 7: ...7 7 1 2 A Door Stop Bracket A should be positioned as shown ASSEMBLY ATTENTION Do not attach rear support screws and washers until Step 6 www weber com...

Страница 8: ...8 ATTENTION Do not fully tighten screws Clips should slide freely when installed ASSEMBLY 3 4 www weber com...

Страница 9: ...9 9 Back ASSEMBLY 5 6 www weber com...

Страница 10: ...10 ASSEMBLY 7 www weber com...

Страница 11: ...g Make sure the frame is resting level on the finished surface of the structure B Adjust the Front Vent to rest squarely on ground 1 1 1 1 1 1 a a b A B ASSEMBLY 8 Clearances 1 24 610 mm Any Surface a...

Страница 12: ...12 S 460 S 660 1 4 6 35 mm Drill Bit ASSEMBLY 9 10 www weber com...

Страница 13: ...ll that are in contact with the island structure This will prevent moisture seepage The sealant you use must have a temperature rating above 120 F 48 8 C m ATTENTION Before applying any silicone seala...

Страница 14: ...CK WIRE 2 GREEN WIRE 3 RED WIRE 4 RED WIRE m WARNING Make sure that all control knobs are turned to the OFF position before connecting the gas supply and operating the grill ASSEMBLY S 660 S 460 1 2 3...

Страница 15: ...Note Secure wire to side panel Requires 3 D alkaline batteries Included Use alkaline batteries only Do not mix old and new batteries or different types of batteries standard alkaline or rechargeable...

Страница 16: ...16 ASSEMBLY 1 2 S 460 S 660 3 1 2 15 16 17 www weber com...

Страница 17: ...17 17 S 460 S 660 C A B Match Holder ASSEMBLY 18 www weber com...

Страница 18: ...18 1 4 6 35 mm Drill Bit ASSEMBLY ATTENTION Before drilling any holes for the rear vent make sure the cookbox is flush with the front of the grill frame 19 www weber com...

Страница 19: ...19 19 s 460 s 660 ASSEMBLY S 460 S 660 20 21 www weber com...

Страница 20: ...20 s 460 s 660 S 660 S 460 ASSEMBLY 22 23 www weber com...

Страница 21: ...21 21 ASSEMBLY s 460 s 660 24 www weber com...

Страница 22: ...22 ASSEMBLY 1 2 25 S 660 S 460 www weber com...

Страница 23: ...r Grill Out Handle Light has a Tilt Sensor Lid up ON Lid Closed OFF The power button a activates or deactivates the Tilt Sensor For daytime use deactivate the sensor by pressing power button a Require...

Страница 24: ...cal Codes you must conform to the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 Natural Gas and Propane Installation Code CSA B149 1 or Propane Storage and Handling Code B149 2 or t...

Страница 25: ...068 8 580 5 900 4 740 4 050 3 590 3 260 3 000 2 790 2 610 2 470 2 190 1 980 1 820 1 700 4 4 026 17 500 12 000 9 660 8 270 7 330 6 640 6 110 5 680 5 330 5 040 4 460 4 050 3 720 3 460 2009 National Fire...

Страница 26: ...sipate outside of the island structure C If the remote LP cylinder enclosure has four sides a top and a bottom and is intended for installation in a built in island enclosure 1 At least one ventilatio...

Страница 27: ...barbecue m WARNING Keep the ventilation openings of the cylinder enclosure free and clear of debris BUILT IN TANK ENCLOSURE INSTRUCTIONS m WARNING Turn off the gas at the LP gas supply cylinder when...

Страница 28: ...ustible materials only NOTE If you have questions on what materials are considered noncombustible contact you local building supplier or fire department m DANGER Use of any other hose and regulator as...

Страница 29: ...4 2 2 Hose and regulator 1 Tank stand 1 Tank stand base 1 Tank Scale 1 1 4 20 nut 6 Nylon washer 12 1 4 20 x 1 2 bolt 6 Cylinder glide 2 1 2 Flare Gasket 2 3 8 Flare Gasket 2 PARTS LIST ASSEMBLY 1 2...

Страница 30: ...e mounting hardware not included mounting the LP hose and regulator Securley mount the hose and regulator bracket to the top of the built in tank enclosure using non corrosive hardware mounting hardwa...

Страница 31: ...through the Island Structure cavity to the hose and regulator connection inside the tank enclosure Shown in illustration 2 Uncap one flare fitting from the 90 Connection on the regulator hose located...

Страница 32: ...ber Compact Grill Configura tion Botswana Weber Canada Smokey Joe Genesis China Kettle Silhouette Denmark Kettle Silhouette Smokey Joe Weber Finland Smokey Joe France Kettle Silhouette Smokey Joe Webe...

Отзывы: