Webasto Frigo Top 10 Скачать руководство пользователя страница 8

Frigo Top 10 - 43 | Pordoi 2000 - 4000 8 

5.4  Change the service interval

Fig. 16:  Interval setting at 2.000 hr

 

3

Make sure that the screen shows “

SEr

The standard service interval is 2.000 hr.

 

 

X

Press “

Set

 

The screen shows the actual service interval

        /   

 

X

Press “

Up

” or “

Down

” to increase or decrease the 

service interval value: 
0 = Service indicator is disabled

100 = 1.000 hr; 
150 = 1.500 hr; 
200 = 2.000 hr;

250 = 2.500 hr; 
300 = 3.000 hr.

 

X

Press “

Set

” to confirm a service interval.

 

SEr

” starts blinking.

 

Screen shows “

SEr

”.

 

After approx. 10 s the display turns back to the 
operating menu.

6  The programming tool or “hot key”

You can program the control element quickly or restore parameter with help of a programming tool, called the “hot key. The hot key 
has 2 functions:

 

Download parameters from the hot key into the control element.

 

Upload parameters from the control element into the hot key.

Uploading parameters from the control element into the hot key provides a back up for eventual restoring parameter settings or to pro-
gram other control elements with the same set of parameters quickly.

6.1  General

Fig. 17:  Slot hot key

 

3

Provide access to the backside of the control element or remove 
the control element from its mounting panel.

 

X

You insert a hot key in the slot at the back of the control element.

Mind the right position of the hot key!

Fig. 18:  Upload / download error in-

dication

The control element shows “

Err

” in case the download 

or upload failed.

 

Switch the control element off and on again to 
restart the download or upload.

or

 

Remove the hot key to stop operation.

6.2  Download parameters to the control element

 

X

Switch off the control element.

 

X

Insert a hot key in the slot at the back of the control 
element.

SET

SET

Содержание Frigo Top 10

Страница 1: ...Workshop Manual Transport Refrigeration Frigo Top 10 43 Pordoi 2000 4000 English F...

Страница 2: ...vel menus 6 4 1 Entering the 1st service level 6 4 2 Entering the 2nd service level 6 4 3 Change a parameter setting 6 4 4 Exit a service menu 6 5 Set and reset the service interval 7 5 1 Enter the se...

Страница 3: ...l Result damage to the refrigeration system X X Follow the operating instructions and instructions described in this document 2 Safety 2 1 General safety The repair and commissioning personnel must ha...

Страница 4: ...compartment 3 3 Service levels The control element has an extensive set of parameters to regu late and control the refrigeration process The parameters are split in 2 levels Level 1 Level 2 Access th...

Страница 5: ...pressor operation count appears on the display preceded by a minus sign Example If the saved value is 1511 hours of operation the first time the button is pressed 001 thousands is displayed The second...

Страница 6: ...irst parameter of the 1st service level The degree symbol starts blinking 4 2 Entering the 2nd service level Fig 06 2nd level service menu Fig 07 First parameter of the 2nd level service menu X XPress...

Страница 7: ...ween SEr change interval rSt reset interval 5 3 Reset the service interval Fig 14 Reset interval No Fig 15 Reset interval Yes 3 3 Make sure that the screen shows rSt ATTENTION Do not reset the service...

Страница 8: ...eters from the hot key into the control element Upload parameters from the control element into the hot key Uploading parameters from the control element into the hot key provides a back up for eventu...

Страница 9: ...t restarts and uses the new parameters X XRemove the hot key 6 3 Upload parameters to the hot key 3 3 Program the control element as desired with the keys on the front 3 3 Leave the control element on...

Страница 10: ...ng the sensor X XContact a Webasto service partner HA Maximum temperature alarm Temperature in cooling compartment is too high LA Minimum temperature alarm Temperature in cooling compartment is too lo...

Страница 11: ...input Potential free contact NTC probe 40 110 C 40 230 F Relay outputs PTC probe 50 150 C 58 302 F Compressor 8 3 A 16 6 A or 20 8 A 250 VAC Defrost 8 3 A 250 VAC Fan 8 3 250 VAC Fig 23 F 32 74 71 29...

Страница 12: ...emeratures compared to the set temperature To be used in case of heating kit n neutral zone disabled cooling only y neutral zone enabled heating kit installed 2 AC Anti short cycle delay minimum inter...

Страница 13: ...ant 0 99 min 2 dFd Temperature displayed during defrost rt real temperature it temperature at defrost start SEt set point dEF dEF label 2 dAd MAX display delay after defrost Sets the maximum time betw...

Страница 14: ...the SET A LU or SET ALL values 2 ALU Maximum temperature alarm when this temperature is reached the alarm is enabled after the ALd delay time SET 110 C SET 230 F 2 ALL Minimum temperature alarm when...

Страница 15: ...pressure switch dur ing the did interval before signalling the alarm event I2F PAL If the nPS activation in the did time is reached switch off and on the instru ment to restart normal regulation 0 15...

Страница 16: ...neutral zone n n n y in case of heating kit 2 AC Anti short cycle delay 1 1 1 2 CCt Continuous cycle duration 0 0 0 2 CCS Set point for continuous cycle 0 0 0 2 COn Compressor ON time with faulty pro...

Страница 17: ...2 ALd Temperature alarm delay 15 15 15 2 dAo Delay of temperature alarm at start up 1 3 1 3 1 3 2 SE Regular service has to be performed x10 hours 200 200 200 2 10 4 6 Digital input Label Description...

Страница 18: ...tt oder der Webseite Ihrer jeweiligen Webasto Landesvertretung Dans le cas d une version r dig e en plusieurs langues l anglais est alors la langue qui fait foi Pour trouver le num ro de t l phone du...

Отзывы: