9.2.2.3 Cover for cold air inlet and hot air outlet
NOTE:
The covers for the cold air inlet and hot air outlet differ. The cover with the smaller opening at the front
must be fitted on the heating air fan. Slide on the covers (3 and 5, Figure 29) until the 4 positioning holes engage
properly in the locking lugs of the lower and upper cover.
9.2.2.4 Grilles (optional) for cold air inlet and hot air outlet
Place the grilles (6, Figure 29, optional) on the covers for the cold air inlet and hot air outlet.
9.2.2.5 Cover for electrical connection
NOTE:
The wiring harness is to be guided out to the left or right of the heater to suit the installation situation.
Slide on the cover (1, Figure 29) until it audibly engages in the upper cover.
Figure 29: Removing/fitting housing parts
1. Cover, electrical connection
2. Top shell
3. Cover, hot air outlet
4. Bottom shell
5. Cover, cold air inlet
6. Grille (on hot air outlet side not shown)
7. Insulators (4 pc.).
8. Widening of corner rib
9.2.3 Replacing control unit
9.2.3.1 Removal
1. Remove heater (see 8.7.1.1).
2. Remove housing parts (see 9.2.1).
3. Remove screws (5, Figure 30).
4. Disconnect connectors on control unit (4).
5. Pull out control unit (4) upward.
NOTE:
No repairs may be carried out on the control unit.
9.2.3.2 Installation
1. Insert plug connections on control unit as shown in Figure 14.
2. Fasten control unit (4, Figure 30) with screws (5).
3. Tighten screws (5) to 3.0 ± 0.3 Nm.