1.0 General Service and Safety Precautions

WARNING

Never service, repair, or troubleshoot this system unless you are a professional air conditioning/refrigeration service person. 
Improper servicing can lead to serious injury or death from fire, electric shock, or explosion.

Refrigeration and air conditioning devices are extremely complicated by nature. Servicing, repairing, and
troubleshooting these products should be done only by those with the necessary knowledge, training, and equipment.

1.1 Refrigerants and Other Chemicals

Contact with refrigerant, mixtures of refrigerant and oil, or other chemicals can cause a variety of injuries including burns 
and frostbite. For example, if refrigerant contacts skin or eyes it can cause severe frostbite. Also, in the event of a 
compressor motor failure, some refrigerant and oil mixtures can be acidic and cause chemical burns.
To avoid injury, wear appropriate protective eye wear, gloves, and clothing when servicing an air conditioning or 
refrigeration system. Refer to your refrigerant supplier for more information.
If refrigerant or mixtures of refrigerant and oil come in contact with skin or eyes, flush the exposed area with water and get 
medical attention immediately.

1.2 System Flushing, Purging, and Pressure Testing for Leaks

Failure to properly flush, purge, or pressure test a system for leaks can result in serious injury or death from explosion, fire or 
contact with acid-saturated refrigerant or oil mists.
Webasto recommends that the system be serviced using a flush and purge station such as a Robinair

®

unit or similar equipment designed for R134a refrigerant systems.
Follow these precautions when flushing/purging a system or pressure testing a system for leaks:

• Use flushing products according to the manufacturer’s instructions.
• To purge a system, use only dry nitrogen.
• When pressure testing for leaks, use only
•  regulated dry nitrogen or dry nitrogen plus trace amounts of the serial label refrigerant, in this case, R134a.
• When purging or pressure testing any refrigeration or air conditioning system for leaks, never use air, oxygen or 

acetylene.

• Oxygen can explode on contact with oil.
• Acetylene can decompose and explode when exposed to pressures greater than approximately 15 PSIG.
• Combining an oxidizing gas, such as oxygen or air, with an HCFC or HFC refrigerant under pressure can result in a 

fire or explosion.

• Use a pressure regulating valve and pressure gauges.

Commercial cylinders of nitrogen contain pressures in excess of 2000 PSIG at 70°F. At pressures much lower than 2000 
PSIG, compressors can explode and cause serious injury or death. To avoid over pressurizing the system, always use a pres

-

sure regulating valve on the nitrogen cylinder discharge. The pressure regulator must be able to reduce the pressure down 
to 1 or 2 PSIG and maintain this pressure. The regulating valve must be equipped with two pressure gauges:

• one gauge to measure cylinder pressure, and
• one gauge to measure discharge or down-stream pressure.

Содержание 5011815

Страница 1: ...le saw kit Refrigerant recovery and recharging machine Weather Pack Metri Pack crimping tool 12085270 1 2 3 Ford Transit 2015 Present 3 5 Liter 148 wheelbase All Roof Heights For kit 5011815 Special i...

Страница 2: ...r repair Webasto heating or cooling system unless you have the proper certifications technical skills tools and equipment required to properly complete the necessary procedures ALWAYS carefully follow...

Страница 3: ...1 3 Scope 8 1 4 Applicability of Manual 8 1 5 Meaning of Warnings Cautions and Notes 8 1 6 Safety 9 1 7 Legal Provisions for Installation 9 1 8 Prohibition on Venting 9 General References 10 Preparat...

Страница 4: ...SE 1 5011008B FITTING REFRIGERANT 90 06THD 06HOSE 1 5011028B FITTING REFRIGERANT 45 06THD 06HOSE 1 5011212B FITTING REFRIGERANT 180 06THD 06HOSE 1 5011166A REFRIGERANT HOSE BURGAFLEX H 10 3090 R 46 FT...

Страница 5: ...134A 2 7LBS 1 901073 HOSE HEATER 0 3215 ID RUBBER 49 FT 901100 HOSE HEATER 0 75 ID GATES BLUE STRIPE 13 FT 5011594A THREADED PLATE M8X1 25 4 5011595A BRACKET LONDON REAR MOUNT TRANSIT 1 62U003AA093A A...

Страница 6: ...death from explosion fire or contact with acid saturated refrigerant or oil mists Webasto recommends that the system be serviced using a flush and purge station such as a Robinair unit or similar equ...

Страница 7: ...Applicability of Manual These non binding installation instructions apply to the make model listed on the front cover of this installation manual Due to optional equipment there may be build variation...

Страница 8: ...iring the removal of refrigerants be serviced by a certified technician under section 609 of the Clean Air Act and that all refrigerant be reclaimed and recycled Vehicle operation must not be impaired...

Страница 9: ...it or any components to the vehicle structure 1 Insert four threaded mounting plates in the locations as shown 2 Install the mounting bracket and London HVAC unit General References Bare sheet metal f...

Страница 10: ...anels drill two 1 3 4 inch 45 millimeters holes five inches 127 millimeters apart Remove the material between the holes and protect the cut edge against corrosion and wire chafing 5 Drill two 1 3 4 in...

Страница 11: ...t secure the coolant pump to the chassis outrigger next to the fuel tank 7 Install the receiver dryer in the receiver dryer mounting clamp Loosely install the trinary switch in the receiver dryer 8 In...

Страница 12: ...r to 4mm 10 Install the condenser reinforcement brackets on the condenser NOTE There are three right angle con denser mounting brackets The long side of the bracket attaches to the condenser assembly...

Страница 13: ...ave to drill three holes One may already have the appropriate threaded insert installed 13 Drill four 3 8 inch holes and install the threaded inserts using an appropriate tool NOTE The A C hose is sho...

Страница 14: ...h making A C hoses A Using blade type hose cutters cut the hose in one cut The cut edge must be clean and flush B Place two properly sized clips in the clip holder The clips should both be facing the...

Страница 15: ...15 Ford Transit London D Lubricate the fitting with PAG oil and insert the fitting until the shoulder of the fit ting is touching the clip holder E Using Oetiker pliers crimp the clips closed...

Страница 16: ...nect a hose between the evaporator high pressure port and the outlet of the receiver dryer 16 Using a 6 45 and a 6 90 fitting connect the receiver dryer input port to the condenser outlet port NOTE In...

Страница 17: ...service fitting to the low pressure port on the London unit using a 10 90 fitting Install the low pressure switch in a location that allows servicing CAUTION Replace hose clamps as necessary Hose cla...

Страница 18: ...alve through the hole drilled in the floor NOTE The following step only applies if you are not using the factory coolant up fitter ports NOTE This is a parallel connection Do not restrict or obstruct...

Страница 19: ...5 8 reducers are used 24 Connect the return and supply hoses to the appropriate up fitter ports NOTE A 3 4 in to 5 8 in adapter may nec essary on the input and output sides of the coolant pump 25 Con...

Страница 20: ...both sides together with a T fitting 28 Route the drain hose from the London HVAC unit assembly down the left rear corner of the vehicle and through the factory supplied hole in the floor Cut the dra...

Страница 21: ...ect the blower motor connector 1 and the thermostat connector 2 31 Connect the low pressure switch 32 Route the wiring harness down the left rear corner of the vehicle Using the provided p clips and t...

Страница 22: ...relay strip mounting panel 33 Mount the relay strip and fuse block to a bracket fabricated for that purpose Route the wiring harness over the wheel well 34 Connect the coolant valve electrical connec...

Страница 23: ...s 37 Drill a 1 25 inch 32 mm hole in the rear of the left foam panel approximately centered between the two indents Route the control panel wiring harness through the hole and to the top center of the...

Страница 24: ...with a 70 amp fuse Reinstall the power distribution center at this time 40 Connect the pink wire to a 12V ignition circuit in the open connector in the battery compartment 41 Connect the positive wire...

Страница 25: ...ord Transit London 42 Cut the dome light bezel and panel to accept the control panel Install the control panel in the dome light bezel 43 Connect and install the control panel and install the package...

Страница 26: ...nsit 44 Connect the condenser fans and the pressure switch on the receiver dryer 45 Connect the coolant pump 46 Using the supplied connector and the proper crimping tool connect the A C compressor ele...

Страница 27: ...leeder valve release trapped air from the system 51 After all the air has been removed from the system fill the reservoir to the proper level 52 While monitoring the system for leaks allow the vehicle...

Страница 28: ...28 Ford Transit Wiring Diagram...

Страница 29: ...29 Ford Transit...

Страница 30: ...the nearest Webasto authorized dealer for warranty service visit http www webasto com or call 800 860 7866 in USA 800 667 8900 in Canada a Limitations Webasto specifically excludes and limits warranty...

Страница 31: ......

Страница 32: ...Webasto Product N A Inc Technical Assistance Hotline USA 800 555 4518 Canada 800 667 8900 www webasto us www techwebasto com Org 3 2016 Rev 12 2021 P N 5011865...

Отзывы: