SECTION 12: USER INSTRUCTIONS
The UHA[X][S] Series heaters are fully automatic
and operate from the external controls fitted on site.
The only user control at the heater is the Manual
Reset Limit Switch -
See Page 32, Section 12.2
.
See Page 44, Section 15.3
for manual reset limit
switch location inside control housing.
12.1 Heater Operation
When the heater has been switched on by the
thermostat installed on site, the main burner will
automatically turn on.
The burner control box will control the safe ignition
of the flame.
All heaters require a constant gas and electricity
supply which must not be interrupted during the
normal operation of this heater.
Should overheating occur, or the gas supply control
system fail to shut off the flow of gas, shut off the
manual gas valve to the utility heater before shutting
off the electrical supply.
Do not use this utility heater if any part has been
under water. Immediately call a qualified service
technician to inspect the heater and replace any gas
control which has been under water.
12.2 Common User Controls
12.2.1 Manual Reset Limit Switch
On residentially approved models, the limit
thermostat is located inside the hinged access door
of the heater.
See Page 44, Section 15.3
. This
control protects against excessive heat build-up
inside the burner compartment.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and service.
Edges are sharp.
WARNING
Failure to follow these instructions can result in death, electric shock, injury or property damage.
Burn Hazard
Allow heater to cool
before service.
Tubing may still be hot
after operation.
Explosion Hazard
Turn off gas supply to
heater before service.
DANGER
Electrical Shock Hazard
Disconnect electric
before service.
Heater must be
connected to a properly
grounded electrical
source.
WARNING
Explosion Hazard
Do not make more than one attempt to
restart the heater if manual reset limit switch
locks out.
The vent or heat exchanger may be blocked.
The fault must be traced and repaired.
Failure to follow these instructions can
result in death, injury or property damage.
Содержание UHA100
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 31: ...SECTION 9 GAS PIPING 23 of 51 Figure 15 Gas Connection ...
Страница 46: ...UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL 38 of 51 14 1 General ...
Страница 60: ......
Страница 61: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......