Страница 1: ...ght the appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cann...

Страница 2: ...CATIONS MODELS HSG200 HSG400 NATURAL OR PROPANE GAS NOTE Dimensions in are informational only English values take priority HSG200 Maximum Input Capacity 200 MBtu HR 211000 kJ Minimum Input Capacity 60...

Страница 3: ...I INSTALLATION A GENERAL The Wayne HSG200 and HSG400 power gas conversion burners are adaptable to most types of central heating plants previously fired by power oil burners Typical heating plants are...

Страница 4: ...of the flue pipe upward 1 4 inch 6 35mm per foot 305m or more Run directly to the chimney fasten joints securely and support horizontal runs to prevent sagging If the flue pipe must be extra long it...

Страница 5: ...ion chamber is normally required to protect non heat transfer surfaces and to provide a radiant bed for rapid heat transfer to the primary surfaces of the heat exchanger If in good condition the exist...

Страница 6: ...00kJ PAGE5 G ELECTRICAL The installation must be wired and GROUNDED in accordance with local codes or in their absence with the National Electric Code ANSI NFPA No 70 1987 or latest edition For the 12...

Страница 7: ...OBERTSHAW TOOO DERHC Figure11 PAGE6 I COMBINATION GAS VALVE The 24 VAC combination gas valve serves three 3 functions 1 manual gas shut off 2 main gas flame pressure regulator 3 automatic electric red...

Страница 8: ...ner operation PAGE7 SECTION II INITIAL START UP 1 NOTE Read the applicable sequence of burner primary gas control operation in Section 3 Operation and Troubleshooting before proceeding 2 Depress the c...

Страница 9: ...EFFICIENCY ssK Figure 12C PAGE8 D The flue gas temperature should be between 325 F 162 78 C and 550 F 287 78 C for domestic gas conversion burners Higher flue gas temperatures indicate overfiring or e...

Страница 10: ...89F GAS PRIMARY PIN 62759 002 W BUILT IN 30 SECOND PREPURGE On a call for heat voltage 24V is applied to motor start relay and air switch Once the fan motor reaches operating rpm combustion air pressu...

Страница 11: ...OR PIN 62530 001 On a call for heat voltage 24V is applied to the motor start relay and air switch The motor relay pulls in the motor After the motor reaches speed the combustion air blower closes the...

Страница 12: ...MULTIPURPOSE METER DISCONNECT WIRE FFOM SENSE TEBMINAL RED BLACK 0 8 uA DC MINMUM AND STEADY O C PAGE11 FLAME SENSING The Honeywell S89 series primary ignition controls utilize the flame current recti...

Страница 13: ...OR DOES NOT START I Check the low voltage transformer for 24 volt output between terminal 3 on the motor start relay either of the T terminals on the control box 2 Check for 24 volts AC between termin...

Страница 14: ...trol Motor starts Completes 30 second prepurge cycle 8 second safe start check series Gas valve opens regulating adequate gas pressure No flame established Primary control locks out after 4 second Hon...

Страница 15: ...OCKS OUT ON SAFETY 1 Reset Control Completes 30 second prepurge cycle and 8 second safe start check Flame is established Sometimes the control locks out before the thermostat or controlling circuit is...

Страница 16: ...ain manual combination valves and main power switch are turned off before opening burner or removing any parts for service A BURNER HEAD AND ELECTRODE SENSOR ASSEMBLY The burner head electrode sensor...

Страница 17: ...642 HSG4OO 5 1t20 D 139 7mm 2 3t16 55 5625mm MOTOR BLOWER ASSEMBLY Figure16 PAGE16 33 DRAWER ASSEMBLY Figure 15 MOTOR SIDEPLATE AU PIN 21658 r I I l i b r r 2 1 16 52 3875mm 23 16 55 5625mm 21642 HSG4...

Страница 18: ...notshown Ootional Pedestal Mountinq notshown PAGE17 PARTS LIST MODEL HSG 200 400 SEE FIG 15 FIG 17 Item Part No Description 1 100934 001 Burner Housing 2 62576 003 Air Tube HSG200 6 152 4mm 63270 004...

Страница 19: ......

Страница 20: ...ing Guide NUISANCE LOCKOUTS FLAME SENSING PROBLEMS HSG200 HSG400 GAS BURNERS Wayne s HSG series direct spark ignition DSI gas burners prove flame through the process of flame rectification Flame recti...

Страница 21: ...ate PAGE 20 LIMITED WARRANTIES FOR OIL AND GAS BURNERS MADE BY WAYNE AND USED IN RESIDENTIAL INSTALLATIONS WAYNE COMBUSTION SYSTEMS WAYNE warrants to those who purchase its Oil Burner Models for resal...

Страница 22: ...lower PAGE21 CONSUMER II ISTRUCTIONS MAINTENANCE o Keep the area around the burner clear and free of com bustible materials gasoline or other flammable liquids or vapors Do not obstruct burner air ope...

Страница 23: ...Notes PAGE22 Notes PAGE 22...

Страница 24: ...Notes PAGE22 Notes PAGE 22...