Seite 21 / 48
5.4. IN 1 Totalization
The totalization function is defined in this menu. This menu will only be showed, if the totalization is active in
Menu IN 1 PROPERTIES.
The totalizator depends on the operation mode. See in the following list.
Operation mode
Totalisation
INPUT 1 TOTAL
INPUT 2 TOTAL
LINKAGE TOTAL
SINGLE
active
0
0
DUAL
active
active
0
IN1 + IN 2
active
active
Total 1 + Total 2
IN1 – IN 2
active
active
Total 1 – Total 2
IN1 x IN 2
active
active
0
IN1 / IN 2
active
active
0
TIME BASE
This parameter defines the time base of the totalization.
It defines the time interval between the recordings of data.
0
SECONDS
The current value is added to INPUT 1 TOTAL every second
1
MINUTES
The current value is added to INPUT 1 TOTAL every minute
2
HOURS
The current value is added to INPUT 1 TOTAL every hour
3
COMMAND
The current value is added to INPUT 1 TOTAL, when using the command (ADD TO
TOTAL 1) for the operation function at the control input (see Command Menu)
DIVIDER
This parameter defines the devisor for the totalization.
0
1
No division
1
10
The result of the totalization is divided by 10
2
100
The result of the totalization is divided by 100
3
1000
The result of the totalization is divided by 1000
DECIMAL POINT
This value defines the position of the decimal point.
0
NO
No decimal point
1
0000000.0
Decimal point at the specified position
2
000000.00
Decimal point at the specified position
3
00000.000
Decimal point at the specified position
4
0000.0000
Decimal point at the specified position
5
000.00000
Decimal point at the specified position
6
00.000000
Decimal point at the specified position
7
0.0000000
Decimal point at the specified position
Содержание WAY-AX