Walk-Through
Mode
(DIP 4 ON)
The PW sensor turns the load OFF three minutes after
the area is initially occupied, if no motion is detected
after the first 30 seconds. If motion continues beyond
the first 30 seconds, the set time delay applies.
High
(DIP #5 OFF)
Default setting. Suitable for most applications.
PIR Sensitivity Adjustment
The PW sensor constantly monitors the controlled environment and
automatically adjusts the PIR to avoid common ambient conditions that can
cause false detections, while providing maximum coverage.
Reduces sensitivity by approximately 50%. Useful in
cases where the PIR is detecting movement outside of
the desired area (also consider masking the lens) and
where heat sources cause unnecessary activation.
Low, 50%
(DIP 5 ON)
Walk-Through
The Walk-Through mode shortens the time delay to reduce the amount of time
the load is ON after a brief moment of occupancy, such as returning to an office
to pick up a forgotten item then immediately exiting.
No Walk-Through
Walk-Through mode disabled.
Alerts
The PW can provide audible and/or visible alerts as a warning before the load
turns OFF.
Unit will beep at one minute*, at 30 seconds and at 10
seconds before turning OFF load. When Walk-Through
is active, the unit beeps three times at 10 seconds
before the load goes OFF.
*If Visible Alert is also ON, the one-minute time-out
warning beep is replaced by the visible alert.
Audible Alerts
(DIP 7 ON)
When only one minute is left in the time delay, the load
connected to the relay turns OFF for one second. This
provides a one minute warning before the load(s) are
turned OFF by the sensor.
Visible Alert
(DIP #6 ON)
No Visible Alerts
(DIP 6 OFF)
No visible warnings provided.
No audible warnings provided.
No Audible Alerts
(DIP 7 OFF)
Call 800.879.8585 for Technical Support